15
After plugging in a circuit protector, it will automatically be parameterised if parameters are available for the
slot in question. Transmission of the parameters will be without interruption of the cyclical data exchange between
the communication unit SVS200-COM and the electronic circuit protector ESX50D-Sxx. After switching the device
on with the ON/OFF button the electronic circuit protector is ready for use.
6.3
Communication via the USB service interface
In addition to the PROFIBUS-DP interface, a maintenance and service interface will also be made available
to the user.
It enables direct access to the bus controller CPC10PB. This is also possible
when there is no
communication via the field bus interface. If the device is in the stand-alone mode, the user can access the
bus controller and the connected electronic circuit protectors at any time (reading or editing) via this interface. The
access in the slave mode can be parameterised by the user via the field bus interface. The delivery conditon
allows only reading access. Editor access has to explicitly be released by the user in the superordinate control
unit.
If the slot parameters are changed, the change will be signalled to the superordinate control unit. The user will
thus be able to process these changes in his control accordingly.
For parameterisation of the individual electronic circuit protectors the corresponding user software
ControlPlex®Views
is available for the USB service interface. This software is available for download from
the E-T-A website and can be installed on a Windows
®
computer. The user software is described separately
in another manual.
7
Communication via PROFIBUS-DP
Depending on the designed configuration a different quantity of data bytes will be exchanged in the cyclical
data traffic between master and slave.
The system allows determination which data volume can be exchanged. Two different modules are selectable
per PWR board with different configurations (4, 8, 12, 16, 20 or 24 slots for the circuit protectors).
The module Control-Measure exchanges I/O data (status/control) and measuring values of the individual circuit
protectors with the master. The module Control only exchanges I/O data (status/control) of the individual circuit
protectors with the master.
The GSD file made available for the projecting tool allows the related configuration, the system recognises all
permitted configurations and processes the cyclical data defined in the projection.
Only the module I/O data CPC10PB-Device is firmly pre-set and cannot be removed because the input bytes
hold vital failure and diagnoses information as described in the following.
The maximum number of input and output data is limited to 244 bytes each.
Not more than 368 bytes must be exchanged in total.