46
HYDRAULIC GENERATORS
OPERATION
5.2. STOPPING THE HG HYDRAULIC GENERATOR
1. Stop the HG by closing the hydraulic control valve.
Picture 34: Stopping the HG hydraulic generator
ATTENTION!
Exceeding the maximum hydraulic flow causes the generator to overspeed
and may damage it as well as the connected appliance. READ CHAPTER
„10. TECHNICAL SPECIFICATIONS“ for the technical specifications.
5.3. AMBIENT TEMPERATURE
To avoid power loss, it is not recommended to use HG hydraulic generator when
the ambient temperature e40 ºC. When the ambient temperature exceeds
+40 ºC power takeoff should be limited in accordance with the attached diagram,
e.g. for instance, at the ambient temperature of +50 ºC the power takeoff should
not be more that 80 % of the maximum.
If the ambient temperature r40 ºC, the HG’s full output power can be
maintained by adding an additional air ventilation.
Picture 35: Power take off in higher temperatures