HYDRAULIC GENERATORS
INSTALLATION
4.5. IP CODE REQUIREMENTS
IP23 HG hydraulic generators must be installed in a location and position where
water can not enter the generator from below or from the sides according to the
IP23 classification. IP54 HG hydraulic generators can be installed outside of a base
machine.
Picture 29: IP23 and IP54 positioning
4.6. OUTPUT FREQUENCY INSPECTION AT START-UP
HG hydraulic generators are tested and adjusted at factory but it is recommended
to check the output frequency before taking HG hydraulic generator into operation.
1. Ensure that the generator is properly connected to the hydraulic system of your
base machine and there are no oil leakages in system.
2. Start the engine of your base machine. Adjust the engine speed to demanded
level if necessary.
3. Start the generator with a control valve.
Picture 30: Starting the HG hydraulic generator
4. Check the output frequency. Use universal true RMS-multimeter. When the
generator is running without load, switch the metering device to the Hz-position
and check the frequency from each socket. Frequency value should be 50 Hz
(60 Hz) ± 5%.