37
RMO60TD DV-Win Software
position is changed for the first time. There should not be any current present in the tap changer motor
drive circuit during this short period of time. Otherwise, the current clamp compensation will be incorrect,
and it will generate incorrect measurement results.
At the end of the test you have to stop the test by pressing
STOP
. The RMO60TD will go to the
“discharging” mode. There will be a question to save the graph.
Note:
The
PAUSE
button is intended for the situations when some occur during the test, in order to handle the
test easier. When
PAUSE
is pressed, at that moment the DV-Win stops recording the graph. Whenever
you release
PAUSE
, the DV-Win continues to record the graph/transitions (dynamic resistance).
Once the measurement is completed, save the data. The graph can be saved as the graph with three
different resolutions:
-
High (resolution is 0,1 ms)
-
Medium (resolution is 1 ms)
-
Low (resolution is 4 ms)
The graph analysis
The graph can be analyzed “online” and “offline”. It is possible to zoom in a part of the graph of the
interest by dragging the left mouse button around the required area.
Toolbar of the graph
Save
Save OLTC graph as a TCP, BMP or JPEG file. If the file is saved as a TCP file, after the test is finished
it is possible to recall the graph and analyze it using DV-Win. If the graph is saved as BMP or JPEG it
can be opened using any picture viewer.