41
RMO60TD DV-Win Software
The Demagnetization function is selected by choosing the
“Demagnetization” tab. Selection of the
starting current is carried out in the drop-down list
“Test current”.
We recommended that the starting current is the same as what was used for the measurement of the
transformer under test. Therefore, the test current used for the last test is displayed as a default one.
The demagnetization is performed by pressing
START
.
Note:
Never remove the current leads during the demagnetization process and always allow enough time for
the transformer being tested to completely demagnetize. Large transformers can require several minutes
to demagnetize.
During the demagnetization process the transformer will be charged and discharged
several times.
Once the demagnetization process is finished, the DV-Win displays the message
“Demagnetization done!”