8 | Maintenance
164
D-R 290
Setting path:
Device (D‑R 290 ) >
> Functions
>
D‑R 290
Service
Functions > Test the
fail-safe shutter
1
or
Device (D‑R 290 ) >
> Functions
>
D‑R 290
Service
Functions > Test the
fail-safe shutter
2
The fail-safe shutter is operating correctly if during the test the shutter closes once and
opens again.
At intervals of approx. 6 months the operational status of the supercaps should also
be tested:
●
Check LED 5 on the control electronics (figure on the left – L5).
The LED will light up if the supercaps charging status is OK.
A possible cause of any malfunction is a defect in the charging electronics or a defec
tive supercap.
In such cases, check the charging electronics (
printed circuit board D-SK AE no.30
mains adaptor) and replace them if they are defective.
Checking the battery in the measuring head
The battery in the measuring head buffers the power supply for the internal clock with
in the measuring head. This clock provides system messages with timestamp.
After a long time in storage without a power supply this battery can become dis
charged. Frequent occurrence of the warning [81] (see
) "Clock not set" may
also indicate a discharged battery.
To change the battery, proceed as follows:
Opening the housing
1.
Open the four quick-release clamps and swing down the measuring unit.
2.
The 6 screws for the housing cover are accessible internally. Undo them in the se
quence specified at the bottom left.
Before undoing the last screw (6) grasp the handle of the housing cover with one
hand, so that the housing cover is supported by the lower arm.
3.
Put the housing cover aside.
Checking the
supercaps
Fig. 8.8: LED 5
8.2.12
Open the housing:
First pull the plug
then open the door
Fig. 8.9: Attachment screws
for the
housing cover
Содержание D-R 290
Страница 12: ...12 D R 290 ...
Страница 18: ...1 General 18 D R 290 ...
Страница 20: ...20 D R 290 ...
Страница 28: ...2 Safety 28 D R 290 ...
Страница 30: ...30 D R 290 ...
Страница 38: ...3 Delivery 38 D R 290 ...
Страница 40: ...40 D R 290 ...
Страница 60: ...4 Product description 60 D R 290 ...
Страница 106: ...106 D R 290 ...
Страница 152: ...152 D R 290 ...
Страница 174: ...8 Maintenance 174 D R 290 ...
Страница 176: ...176 D R 290 ...
Страница 177: ...9 Appendix D R 290 177 Appendix Measurement point questionnaire Fig 9 1 Measurement point questionnaire 1 9 9 1 ...
Страница 178: ...9 Appendix 178 D R 290 Fig 9 2 Measurement point questionnaire 2 ...
Страница 188: ...9 Appendix 188 D R 290 Fig 9 11 Dimensional diagram D TB 100 supply unit Dimensional diagram purge air unit D BL 9 3 7 ...
Страница 193: ...9 Appendix D R 290 193 Fig 9 18 Dimensional diagram weather protection cover control electronics protective device ...
Страница 194: ...9 Appendix 194 D R 290 ...
Страница 200: ...11 Index 200 D R 290 ...
Страница 202: ...GmbH Kollaustraße 105 22453 Hamburg Germany www durag com ...