Specifications
057-281 ISSUE: 1
Page 12 of 58
2.11 COMMUNICATIONS
2.11.1 CAN
NOTE: For further details of CAN communication, see the section entitled CAN Interface
Specification elsewhere in this document.
Parameter
Description
Protocol
S.A.E. J1939.
Bit Rate
250 kb/s
Isolation
±2.5 kVrms
Termination
120
Ω termination resistor, with the option for direct PCB
installation.
2.11.2 CONFIGURATION PORT
NOTE: For further details of module configuration, refer to DSE Publication: 057-283
DSEA108 Configuration Suite PC Software Manual.
In conjunction with the DSE815 Configuration Interface, the Configuration Port is provided to give a
simple means of connection between a PC and the controller.
Using the DSE Configuration Suite Software, the operator is then able to monitor the device and
perform reset operations.
Additionally, the various operating parameters are available to be viewed or changed.
To connect a module to a PC by USB, the following items are required:
•
DSEA108
•
DSE815 Configuration Interface
•
DSE Configuration Suite PC Software (available from www.deepseaplc.com).