Setup Procedure
057-281 ISSUE: 1
Page 26 of 58
4.3.2.5
SOFT START RAMP
Once the stability settings have been
completed, the
Soft Start Ramp
values can be
set.
The
Ramp Start Point
value determines the percentage of the configured voltage
Set Point
at which
the
Soft Start Ramp
takes effect. If a voltage spike at a value below the voltage
Set Point
is shown on
start up, decrease this value. The settings should then be adjusted to allow for the smoothest start up
in the optimum time for your application.
The Ramp Rate value determines how fast the voltage ramps up from the Ramp Start Point to the Set
Point on start up. If excessive overshoot past the Set Point is seen, decrease this value. The settings
should then be adjusted to allow for the smoothest start up in the optimum time for your application.