Setup Procedure
Page 19 of 58
057-281 ISSUE: 1
Open the selected
Stability Configuration
page.
Ensure the
Proportional
and
Integral
Preset Enable
options are checked, and set the
Preset Range
of both
to 100 %.
Set the
Derivative Set Point
to 0.
Set the
Maximum Duty Cycle
to 100 %. Leave all other
Excitation Output
values at default.
Leave the
Soft Start
values at default for the first start. If
an excessive voltage spike occurs on start up, reduce
the
Ramp Start Point
.
Choose the
Protections
tab and set
Start-up Fail Delay
to its maximum
value. This prevents it interfering with
the setup process.
Preset Enable
remains ‘checked’
Preset Enable
remains ‘checked’