Setup Procedure
Page 33 of 58
057-281 ISSUE: 1
4.4.2 ALTERNATE VOLTAGE RANGE
DIP Switch
Function
Off
On
1
Voltage Sensing Range
90 V to 300 V
180 V to 600 V
DIP Switch 1 selects the Voltage Sensing Range. Any adjustments to the presets affect the selected
range. To adjust the alternative range, first change the DIP switch position.
With the generator set stopped, observe the settings on the SCADA
Diagnostic
display and turn the
presets to the desired positions.
4.4.3 ALTERNATE FREQUENCY RANGE
NOTE: The Alternate Frequency Range DIP switch is not functional when the Auto
Frequency Detection function is enabled. For further details of module configuration, refer to
DSE Publication: 057-271 DSEA108 Configuration Suite PC Software Manual.
DIP Switch
Function
Off
On
2
Frequency Range
50 Hz
60 Hz
DIP Switch 2 selects the Frequency Range. Any adjustments to the presets affect the selected range.
To adjust the alternative range, first change the DIP switch position.
With the generator set stopped, observe the settings on the SCADA
Diagnostic
display and turn the
presets to the desired positions.
4.4.4 ALTERNATE STABILITIES
While the AVR is provided with four alternative
Alternator Stability
configurations, it is not intended
that an AVR is switched between them after setup as this would require the entire stabilisation
procedure to be carried out again for the new selection.
4.4.5 PROTECTIONS
Verify the setting on the
Protections
menu.
Change
Start-up Fail Delay
to the
desired time (this was changed earlier
in the setup procedure to ease the
setup process), the factory default 3.0
seconds is suitable for most generator
sets.
Use the SCADA section of the
Configuration Suite PC Software to
check the
Excitation Voltage
during
normal operation, at a high load level.
Set the
Over Excite Trip
slightly above
this level.
Содержание DSEA108
Страница 1: ...ISSUE 1 DEEP SEA ELECTRONICS PLC DSEA108 Operator Manual Document Number 057 281 Author Jack Zochling...
Страница 15: ...Installation Page 15 of 58 057 281 ISSUE 1 3 2 1 AUXILIARY WINDING CONNECTION...
Страница 16: ...Installation 057 281 ISSUE 1 Page 16 of 58 3 2 2 SHUNT CONNECTION...
Страница 57: ...This Page is Intentionally Blank...
Страница 58: ...This Page is Intentionally Blank...