
C h a p t e r 2 : A d v a n c e d P r o g r a m m i n g
5 0
2.3.21Installer
Lockout
If
Installer Lockout
is selected a hardware default cannot be performed.
When
Installer Lockout Disable
is selected the system will restore all programming to
factory defaults if a hardware or software default is performed.
To enable or disable Installer Lockout perform the following:
1. Enter Advanced Programming.
2. To enable Installer Lockout, enter section [990]. To disable Installer Lockout, enter
section [991].
3. Enter the Installer Code.
4. Enter section [990] or [991] again.
Installer Lockout Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Section [990]
Installer Lockout Disable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Section [991]
2.3.22Walk Test
The
Installer Walk Test
can be used to test the alarm state of each zone of the system.
Before beginning the walk test, ensure the following conditions are met:
1. The system is disarmed
2. The Keypad Blanking option is disabled (section [016]: [3])
3. The
Fire Bell is Continuous
option is disabled (section [014]: [8])
4. The Transmission Delay is disabled, if Transmission Delay is not required (section
[370])
NOTE:
Fire Troubles are not supported in Walk Test.
To perform a Walk Test, do the following:
1. Enter Advanced Programming
2. Enter Section [901]
When any zone is violated the system will activate the Bell Output for two seconds, log the
event to the Event Buffer and communicate the alarm to the central station. Each zone
should be tested several times during the test. Check the event buffer to ensure that all
zones and FAP keys are functioning properly.
NOTE:
The transmission delay timer will affect the communication of events
during walk test mode.
To stop the test, you must do the following:
1. Enter Advanced Programming
2. Enter Section [901]
Zones do not have to be restored to stop the test.
NOTE:
The Alarm Memory is cleared upon entering Walk Test mode.