
3 3
Section 2.3: Changing Other NT9010 Functions
Most installations will only require basic programming. You can complete the basic programming using the NT9010’s
Flash Programming (please see
Chapter 1: Quick Set Up
for more information). This section explains programmable
features that affect the internal functioning of the system, including zone operation, central station communications,
talk/listen-in features, computer downloading features, and other advanced options.
2.3.1 Zone
Definitions
You can change how each of the 32 zones will operate in programming sections [001] -
[004]. For each zone that will be used, enter a 2-digit zone definition.
NOTE:
In addition to selecting how each zone will operate, attributes may be
programmed by zone (see 2.3.2 Zone Attributes on page 35).
NOTE:
PIR’s covering entry/exit zones should be type [06] Delay Stay/Away.
[00]
Null Zone:
The zone will not operate in any way. Zones that are not used should
be programmed as Null zones.
[01]
Delay 1 Zone:
If this zone is violated when the system is armed it will provide an
entry delay. The keypad buzzer will sound to warn the user that the system must
be disarmed. If the system is not disarmed before the entry delay expires an
alarm will be generated. Typically this type of zone will be used for the front
door, back door or any other entry/exit point. Refer to Section [005], “System
Times”, to program the Delay 1 zone entry delay time.
[02]
Delay 2 Zone:
This zone type operates the same as the Delay 1 zone option but
can provide a different entry delay. Typically this zone will be used for a garage
door. Refer to Section [005], “System Times”, to program the Delay 2 zone entry
delay.
[03]
Instant Zone:
If this zone type is violated when the system is armed it will cause
an instant alarm. Typically this zone is used for windows, patio doors or other
perimeter type zones.
[04]
Interior Zone:
If this type of zone is violated when the system is armed it will
follow entry delay if a delay type zone was violated first. Otherwise it will cause
an instant alarm. Typically this zone is used for interior protection devices, such
as motion detectors.
[05]
Interior Stay/Away Zone:
This zone type works the same as the Interior zone
type with one exception. The zone will be automatically bypassed under the fol-
lowing conditions:
■
the system is armed in the Stay Mode (see
2.2.10 Function Keys
on page 28)
■
the system is armed without entry delay (see
[*] [9] Arming Without Entry
Delay
on page 28)
■
the system is armed with an access code and during the exit delay a Delay type
zone is NOT tripped
The automatic bypass avoids having the user manually bypass interior type zones
when arming at home. If automatically bypassed, the user can reactivate the
zones by entering the [
✱
][1] command (see
[*] [1] Zone Bypassing
on page
25). Typically this zone is used for interior protection devices, such as motion
detectors.
[06]
Delay Stay/Away Zone:
This zone type will operate the same as the Interior
Stay/Away zone type except that it will always provide entry delay. Typically this