30
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Table 30-1:
Setup menu
Menu item
Default value
Minimum
value
Maximum
value
Units
Notes
Note: Your system might not have all of the items listed in this table (Pages 30 through 36) .
TDS settings (not available in Europe)
High TDS causes?
Alarm and
message
Message only
Alarm and
message
--
Alarm will occur at 75 ppm if configured to alarm
for High TDS . Message will occur at "TDS message
setpoint" setting .
TDS message setpoint
50
25
75
--
Input signal
RH transmitter
--
--
--
--
Transmitter enabled
--
No
Yes
--
RH set point
35
0
100
%
RH offset
0
-20
20
%
DriSteem recommends using default values for offsets
and PID settings when first setting up your humidifier .
PID tuning
--
--
--
--
RH PID band
10
0
50
%
Proportional gain
80
0
1000
---
Integral gain
40
0
1000
---
Derivative gain
0
0
1000
---
Dew pt transmitter
--
--
--
--
Transmitter enabled
--
No
Yes
--
Dew point set point
50
20
80
°F
10
-6
26
°C
Dew point offset
0
-20
20
°F
DriSteem recommends using default values for offsets
and PID settings when first setting up your humidifier .
0
-11
11
°C
Dew point minimum
0
-100
Maximum
°F /°C
Dew point maximum
100
Minimum
100
°F /°C
PID tuning
--
--
--
--
Dew point PID band
10
1
20
°F
5
1
20
°C
Proportional gain
80
0
1000
--
Integral gain
40
0
1000
--
Derivative gain
0
0
1000
--
Continued
INSTALLATION
Step 2 – Setup