![DriSteem Vapor-Logic Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/dristeem/vapor-logic/vapor-logic_installation-and-operation-manual_2531533070.webp)
66
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
DRAINING WHEN USING SOFTENED WATER
When using softened water, draining occurs for a one-minute duration after
a period of time based on 1000 hours of 100% operation to remove residue
from the drain valve mechanism . End-of-season draining occurs as described
below .
SKIM TIMER
With a tap/softened water configuration, the Vapor-logic controller has a skim
timer . This timer is activated at the end of each fill cycle . The timer keeps the
fill valve open (for a user-determined amount of time after the tank has filled) to
skim minerals off the water surface . The skim time is adjusted through the Setup
menu .
END-OF-SEASON DRAIN
If there is no call for humidity for a user-defined time period, the humidifier
performs an end-of-season (EOS) drain where the drain valve remains open for
ten hours to allow the tank to drain and then closes . If the humidifier receives
a call for humidity after the ten-hour end-of-season drain-down period has
begun, the controller stops the end-of-season draining, the tank refills, and the
humidifier resumes normal operation . The user-defined inactivity time period
(idle time) is defined in the end-of-season drain section of the Setup menu . This
option is available only on units equipped with electric drain and fill valves .
SERVICE INTERVAL
The Vapor-logic controller tracks the amount of water converted to steam by the
humidifier and the number of hours the humidifier runs . When the amount of
steam or hours of run time exceeds the user-defined service interval (pounds,
kilograms, or hours, adjusted in the Setup menu), “Service unit” appears in the
Messages Log .
The humidifier continues to operate after the message appears . The message
notifies the user that the service interval was reached and the humidifier should
be cleaned . The message remains in the Messages Log until it is cleared or
until the Messages Log adds 10 new messages (the maximum number of
messages the log holds) .
Options and features
OPERATION