![DriSteem Vapor-Logic Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/dristeem/vapor-logic/vapor-logic_installation-and-operation-manual_2531533036.webp)
32
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Table 30-1:
Setup menu (continued)
Menu item
Default value
Minimum
value
Maximum
value
Units
Notes
Water management
Drain valve
(not an XT menu item)
--
--
--
--
Changing drain valve settings requires changing
the drain valve . Not all options available for all
models .
Type
Model-specific
Damper
(Honeywell
®
)
Motorized
(Belmo
®
)
--
Actuator
Electric
Manual
Electric
--
Status
Normally closed
(N .C .)
Normally
closed (N .C .)
Normally
open (N .O .)
--
Drain tempering
Enabled
Disabled
Enabled
--
Auto drain/flush
(not an XT menu item)
--
--
--
--
Auto drain/flush requires a humidifier with an
electric drain valve . Not all options available for all
models .
Drain/flush enabled
--
No
Yes
--
When enabled, the humidifier automatically drains
and then flushes the tank at user-defined intervals .
Usage
Model-specific
0
2,200,000
lbs
Select amount of water to be converted to steam
before auto drain/flush starts .
0
1,000,000
kg
Schedule enabled
--
--
--
--
Allowed days
--
--
--
--
Select days of week auto drain/flush is allowed
once usage requirement is met .
Sunday
Yes
No
Yes
--
Monday
Yes
No
Yes
--
Tuesday
Yes
No
Yes
--
Wednesday
Yes
No
Yes
--
Thursday
Yes
No
Yes
--
Friday
Yes
No
Yes
--
Saturday
Yes
No
Yes
--
Time to drain/flush
0
0
23
--
Select time of day (24 hour clock) auto drain/flush
starts once usage requirement is met .
Drain duration
Model-specific
0
120
Minutes
Select number of minutes for drain valve to remain
open during auto drain/flush . Default value is
based on tank and valve size .
Flush duration
Model-specific
0
15
Minutes
Select number of minutes for fill valve to remain
open during flushing .
Continued
INSTALLATION
Step 2 – Setup