VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Table 46-1:
Diagnostics menu
Menu item
Minimum
value
Maximum
value
Notes
Note: Your system might not have all of the items listed in this table (Pages 46 through 48) .
Download data
Download to USB
--
--
Download all data sets to the USB flash drive .
Download via Ethernet
--
--
Only available from web page
Data point interval
30 seconds
900 seconds Interval that data will be stored
USB backup/restore
Back up settings
No
Yes
Humidifier settings can be backed up to or restored from a USB flash drive .
Restore settings
No
Yes
Humidifier info
Factory string
--
--
Displays as-shipped configuration string
Current string
--
--
Displays current configuration string
Serial number
--
--
Displays humidifier serial number
Firmware version
--
--
Displays current firmware version of Vapor-logic control board
Firmware date
--
--
Displays current firmware date of Vapor-logic control board
Model
--
--
Voltage
--
--
XT systems only
Phase
--
--
XT systems only
Test outputs
Fill valve
--
--
Cycles output to verify operation .
Pulse fill valve
--
--
Universal water systems
Note:
Humidifiers with the universal water system use the same conductivity probes found in
the three-probe system . Additional valves and software algorithms measure and control
the water level for optimum operating efficiency . All water types and conductivities
work with the universal water system . Vapor-logic automatically provides steady steam
output while maintaining the water level between the bottom and middle probes .
The humidifier will periodically perform probe checks to insure that the probes are
being read accurately and to determine the quality of the incoming water . If the signal
from the probe assembly begins to deteriorate, the “Clean probes” message appears
in the Messages Log . Once the probe system reaches its maximum usable life, the
humidifier shuts down and the “Faulty water probe” alarm appears .
Drain valve
--
--
Cycles output to verify operation .
Fan control
--
--
Dry contact relay 1 or 2
--
--
Inlet valve
--
--
Relief valve
--
--
RO pump
--
--
Continued
Diagnostics screen
OPERATION