VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Test outputs and test run
TEST OUTPUTS
When completing an installation or repair, cycle all outputs, such as fill valve,
drain valve, etc ., to verify operation . Go to the test outputs section of the
Diagnostics menu and scroll through each connected output to verify operation .
During testing, the humidifier mode changes to Standby and the tank status
changes to Test .
TEST RUN
Vapor-logic has a test run capability to confirm system functionality . This
capability allows a technician to simulate a demand for steam production
when there isn’t one (such as when performing routine maintenance) . To
confirm functionality, go to the test run section of the Diagnostics menu . Set
system demand percent and set test run time duration . During testing, the
humidifier mode changes to Standby and the tank status changes to Test .
mc_102108_1350
OPERATION
1 . Prepare a new flash drive as described in Step 3 of “Downloading
firmware updates” on Page 69 .
2 . Repeat Steps 4 through 11 in Table 70-1 .
3 . Repeat Steps 1 through 7 on Page 72 .