VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Table 30-1:
Setup menu (continued)
Menu item
Default value
Minimum
value
Maximum
value
Units
Notes
Demand signal
--
--
--
--
VDC signal
--
--
--
--
VDC signal enabled
--
No
Yes
--
0% output at
1 .0
0 .0
Maximum
VDC
100% output at
9 .0
Minimum
10 .0
VDC
mA signal
--
--
--
--
mA signal enabled
--
No
Yes
--
0% output at
4 .0
0 .0
Maximum
mA
100% output at
20 .0
Minimum
20 .0
mA
Control via Modbus
--
--
--
--
Choose Modbus, BACnet, or LonTalk in this section
only if your demand input signal is via Modbus,
BACnet, or LonTalk . If you are interoperating (sharing
operating parameters with a building automation
system) using Modbus, BACnet, or LonTalk protocols,
see also the Communications Setup options .
Modbus controlled
No
No
Yes
--
Control via BACnet
--
--
--
--
BACnet controlled
No
No
Yes
--
Control via LonTalk
--
--
--
--
LonTalk controlled
No
No
Yes
--
Humidistat
--
--
--
--
Humidistat enabled
No
No
Yes
--
Limit control
HL switch
--
--
--
--
Switch in system
Yes
No
Yes
--
HL transmitter
--
--
--
--
Transmitter enabled
No
No
Yes
--
Duct HL set point
80
5
95
% RH
Duct HL span
5
0
20
% RH
Span (throttle span) is an offset below the high limit
set point where the humidifier reduces output but
does not turn off until the device high limit set point is
reached .
Duct HL offset
0
-20
20
% RH
Water type
(not an XT menu item)
Potable enabled
--
No
Yes
--
WARNING
Water type setting
Changing the water type setting from potable/
softened to DI/RO, or from DI/RO to potable/
softened requires humidifier hardware changes .
Changing the water type setting without the required
hardware changes can cause component failure,
severe property damage, severe personal injury, or
death .
Softened enabled
--
No
Yes
--
DI/RO enabled
--
No
Yes
--
Continued
INSTALLATION
Step 2 – Setup