8-5
CH 8/ Reports
EN50160 Compliance Limits
Compliance
limits
The table below indicates the limit numbers or range of values required for each
parameter to pass QOS compliance and satisfy EN50160 standard.
Continued on next page
Parameter
Limits for QOS Compliance to Pass
Un = Low Voltage (LV) Supply nominal voltage, upper limit 1kV
Uc = Medium Voltage (MV) Supply Characteristics - declared voltage, range 1kV to 35kV
Power frequency with
synchronous connection to an
interconnected system
Mean value over 10 seconds
•
±
1% during 95% of one week
•
±
4% during 100% of one week
Power frequency with no
synchronous connection to an
interconnected system
Mean value over 10 seconds
•
±
2% during 95% of one week
•
±
15% during 100% of one week
Magnitude of the supply voltage
(In low voltage systems, declared
and nominal voltage are equal)
Mean rms over 10 minutes
•
±
10% of Un or Uc during 95% of one week
•
±
10% to 15% of Un during 100% of one week
Supply voltage variations (Under
normal operating conditions,
excluding situations arising from
faults or voltage interruptions)
Mean rms over 10 minutes
•
±
0% of Un or Uc during 95% of one week
• ±10% to 15% of Un during 100% of one week
Flicker
Plt < 1 for 95% of the time
Also 5% normal, 10% infrequent for LV, 4 &6
for MV
Supply voltage dips
No criteria specified, just reported in DISDIP
table
Short interruptions of the supply
voltage
<1 second for 70% of the short interruptions
Temporary power-frequency
overvoltage between live
conductors and earth
1.5kV for LV
170% for solid or impedance earth,
200% unearthed of resonate earth
Transient overvoltages between
live conductors and earth
Short duration surges: <1 us
Medium duration surges: >1 to <100 us
Long duration surges: >100 us
Supply voltage unbalance
(Under normal operating
conditions)
10 minute mean rms values of the negative phase
sequence component/positive phase sequence
component
• <2% during 95% each period of one week
Содержание PowerVisa
Страница 1: ...PowerVisaTM USER S GUIDE DRANETZ BMI 1000 New Durham Road Edison New Jersey 08818 4019...
Страница 13: ...xiii Dranetz BMI PowerVisaTM...
Страница 14: ......
Страница 78: ...4 16...
Страница 136: ...6 22...
Страница 158: ...7 22...
Страница 204: ...A 10...
Страница 221: ...C 5 APPENDIX C Battery Specifications and Replacement Procedure Battery removal diagram...
Страница 222: ...C 6...
Страница 224: ...D 2...
Страница 248: ...F 4...
Страница 251: ...LEVEL 100 1 Start Menu Automatic Setup MARK101a MARK104 MARK103a G 3 MARK100 To Level 001 VISA123 MARK104a...
Страница 257: ...LEVEL 150 Instrument Settings MARK151 VISA152 PVISA155 MARK156 MARK157 MARK158 MARK160 MARK159 G 7...
Страница 259: ...MARK201 LEVEL 200 Scope Mode MARK202 MARK205 G 9...
Страница 260: ...MARK301PG LEVEL 300 1 Meter Mode Standard MARK302PG MARK303PG MARK305PG MARK307PG MARK306PG MARK304PG G 10...
Страница 261: ...LEVEL 300 2 Meter Mode Distortion MARK315PG MARK313PG MARK314PG MARK312PG MARK316PG MARK311PG G 11...
Страница 268: ...Level 112_601 Advanced Options Journal Interval MARK112_401 MARK112_402 MARK112_403 MARK112_404 MARK112_405 MARK112 G 18...
Страница 269: ...MARK112b LEVEL 112_701 Advanced Options EN50160 Options MARK112c G 19...
Страница 272: ...MARK431 LEVEL 430 Trend MARK432 MARK437b MARK433PG MARK436 MARK434 MARK435 MARK438 MARK440 MARK441 MARK439 MARK437 G 22...