6-20
EN50160 Power Quality
EN50160 Power Quality (for strict EN50160 monitoring only)
Advanced setup
options for
EN50160
EN50160 is a statistical analysis of power quality data based on the EN standard. The
statistical package called Quality of Supply (QOS) is built into the PowerVisa, with
monitoring and setup protocols set to determine voltage measurement compliance
required for EN50160 monitoring. The EN50160-required measurement parameters
include Power Frequency, Supply Voltage Variations, Rapid Voltage Changes, Supply
Voltage Unbalance, Harmonic Voltage, Interharmonic Voltage, and Mains Signalling.
The monitoring site is said to be IN COMPLIANCE if the statistical value over one (1)
week for the specified parameters is 95% or greater.
EN50160 Options setup allows users to define up to five mains signalling frequencies
below 3 KHz. Users can also select pre-defined values for main voltage characteristics
of electricity supplied by Low Voltage (LV) and Medium Voltage (MV) public
networks.
NOTE
EN50160 is defined for the electricity supplied at the supply terminals, and does not
deal with the supply system or consumer’s installation or electrical equipment itself.
Since the standard deals with the voltage characteristics which can be expected in
public distribution networks, other aspects essential for supply quality (i.e. short circuit
power) are not treated within the scope of the standard. EN50160 standard is applicable
only under normal operating conditions of the supply system.
EN50160
optional settings
Continued on next page
Action...
Result...
STEP 1: From the Choose
Monitoring Mode screen, select
EN50160 Power Quality, then
press Next to display Advanced
Options for EN50160.
• If the default settings for the
EN50160 PQ monitoring are
acceptable without change,
press
Next
. The Site Name/
Memory Card screen will
appear. See pages 5-20 to 5-23.
• To review and/or modify
threshold settings for EN50160
monitoring, press
EN50160
Options
. Proceed to Step 2 on
page 6-21.
• Press
Cancel
to quit and return
to Start menu.
MARK112b
Содержание PowerVisa
Страница 1: ...PowerVisaTM USER S GUIDE DRANETZ BMI 1000 New Durham Road Edison New Jersey 08818 4019...
Страница 13: ...xiii Dranetz BMI PowerVisaTM...
Страница 14: ......
Страница 78: ...4 16...
Страница 136: ...6 22...
Страница 158: ...7 22...
Страница 204: ...A 10...
Страница 221: ...C 5 APPENDIX C Battery Specifications and Replacement Procedure Battery removal diagram...
Страница 222: ...C 6...
Страница 224: ...D 2...
Страница 248: ...F 4...
Страница 251: ...LEVEL 100 1 Start Menu Automatic Setup MARK101a MARK104 MARK103a G 3 MARK100 To Level 001 VISA123 MARK104a...
Страница 257: ...LEVEL 150 Instrument Settings MARK151 VISA152 PVISA155 MARK156 MARK157 MARK158 MARK160 MARK159 G 7...
Страница 259: ...MARK201 LEVEL 200 Scope Mode MARK202 MARK205 G 9...
Страница 260: ...MARK301PG LEVEL 300 1 Meter Mode Standard MARK302PG MARK303PG MARK305PG MARK307PG MARK306PG MARK304PG G 10...
Страница 261: ...LEVEL 300 2 Meter Mode Distortion MARK315PG MARK313PG MARK314PG MARK312PG MARK316PG MARK311PG G 11...
Страница 268: ...Level 112_601 Advanced Options Journal Interval MARK112_401 MARK112_402 MARK112_403 MARK112_404 MARK112_405 MARK112 G 18...
Страница 269: ...MARK112b LEVEL 112_701 Advanced Options EN50160 Options MARK112c G 19...
Страница 272: ...MARK431 LEVEL 430 Trend MARK432 MARK437b MARK433PG MARK436 MARK434 MARK435 MARK438 MARK440 MARK441 MARK439 MARK437 G 22...