Instructions for installation, setup and operation - FP9000E
Page
10
of
20
drops). The active state of the input, NC (Normal closed) or NO (Normal open), can be
configured through the panel setup menu.
Rel 1ST
(NO/COM) – Dry contact relay output. The relay is activated in case of Fire Alarm Stage
1 operation mode.
Rel 2ST
(NO/COM) – Dry contact relay output. The relay is activated in case of Fire Alarm Stage
2 operation mode.
Fault
– Open collector output. The output is activated in case of fault in the control panel.
Fire
– Open collector output. The output is activated in case of Fire in the control panel.
Exting
(Extinguishing output, EN 12094-1) – Supervised output for activation of solenoid which
starts the extinguishing automatics.
S 1
– Monitored sounder output. The output is activated in case of Fire Alarm Stage 1 detected in
Zone 1 or Zone 2 or Zone 3
S 2
– Monitored sounder output. The output is activated in case of Fire Alarm Stage 2 detected in
Zone 1 and Zone 2 – both zones are activated.
+ 28V / GND
, 1.0A. Auxiliary output for power supply of external devices.
OK1
– Open collector output. The output changes its state when the three-position key selector
switch is set to “DISABLED” operation mode, or it activates input “ON/OFF Exting”. Both
actions are about disabling the extinguishing process.
OK2
– Open collector output. The output changes its state when the three-position key selector
switch is set to “MANUAL” operation mode.
OK3
– Open collector output. The output changes its state in case of “Low pressure” activation
event.
OK4
– Open collector output. The output changes its state in case of “Hold” activation event.
5.3 Connecting Fire detectors.
Line 1 and Line 2 are extinguishing zones. Use 2-wire cross-zoning connection of the detectors in
the flooding area. The extinguishing in the protected area will start only when Line 1 AND Line 2 are
activated and the panel is in Fire Alarm Stage 2 operation mode. The extinguishing process will not start
if only Line 1 or Line 2 is activated. Line 3 is a conventional fire alarm zone. Use 2-wire connection of
automatic fire alarm detectors and call point in the protected area. Activation of Line 3 starts Fire Alarm
Stage 1 operation mode and activates the 1 Stage Relay output on the PCB control panel.
Fire detectors are installed
to the panel with the help of two-wire insulated line of total
resistance up to 100
. The recommended conductor cross-section is depending on the length of the lines,
which are:
Upon accession to the Fire alarm line to the panel, a check on the resistance is recommended. In
case of proper installation in one line (fitted with finite element) between the plus and minus of the cable
entering the panel, resistance should be measured 4,7k (+/-10%). When measuring the two wires to
"Earth", there should not be a connection.
The connection is made to the terminals of the relevant modules - "+Lx" and "-Lx" (where "x" is
the line number) when observing the indicated polarity. (Fig.2)