Instructions for installation, setup and operation - FP9000E

 

 

Page 

18

 of 

20

 

 

"on"

 and 

"off"

, respectively for disabled function on and off. 

The forbidden line is off (not supplied) and it is not controlled for activated Fire alarm and Fault. 

The  disabled  controllable  output  is  switched  off  (the  executive  device  can  not  be  activated)  and  is  not 

monitored for failure. 

 

LED indication

 - light indicators: 

-

 

"DISABLE"

 lights up with a constant yellow light 

-

 

"

1 2 3

" local line indicator lights up with flashing yellow light. 

-

 

"S 1"

 flashes when a disabled controllable output. 

 

Beeper indication

 - not affected by the disabled component condition. 

 

Text messages indication

 - Information about the lines and controllable outputs in Disabled, are 

displayed on the display.  When 

"on"

 we have a disabled component in 

"off"

 active. 

 

8.7 Test condition 

Panel enters Test condition through manual operation for setting a Fire alarm line in to test. The 

condition is managed through screens of Information and control condition. Menu 

«Test Lines» 

is fourth 

from the main menu.

 

 After  selecting  the  respective  line,  with  the  button  switch  conditions 

"on"

  and 

"off"

respectively, on and off Test function. 

 When inserting the line test, the following changes are in effect: 

 Upon registration of Fire event in the line, sound and light indications and associated controllable 

and relay output for failure are not activated, ie the panel does not enter Fault Condition: 

 - Events in the line are not saved in the energy independent achive; 

 - The line is reset (shuts off its power supply for time 3sec) automatically every 60s. 

 

LED indication

 - light up indicators: 

 - "

TEST

" is lit with yellow light 

 - " 

1 2 3 

" local line indicator in Test lights up with flashing yellow and red light. 

 

 

Beeper

 

indication

 - is not affected by the of the Test condition lines. 

 

 

Text

 

messages

  -  Information on the lines  in  Test  are  displayed on the display.  When  "

on

"  we 

have a line in Test and when "

off

" - no line in Test. 

 

8.7.1. Test leds 
Testing of LED indication the panel done by menu «Test indication». 

  With button  

 activate the illumination of all LEDs. The exception is the indicator for systemic failure 

that should not be on.  With button 

 start the test. If button 

 is not pressed, the panel automatically 

enters Duty condition after 30 seconds. 

 

9 INFORMATION AND CONTROL CONDITION 

 The  panel  has  a  display  and  keyboard  to  check  the  parameters,  settings,  monitoring  and  changing 
conditions,  displaying  arcihves  of  events  and  etc.  From  the  menus  can  be  selected  more  than  50  active 
screens for setup and management of the panel. 
 By menus you can perform the following actions: 

Main menu

: /access level 1 or 2/ 

Содержание FP9000E

Страница 1: ...com web www dm teh com Address Pleven Bulgaria 5800 16 Nikolay Haytov Str DMTech Ltd Pleven Bulgaria 16 Nikolay Haytov Str Tel 359 64 801 597 e mail office dm teh com Page 1 of 19 DMTech Ltd Pleven Extinguishing Control Panel FP9000E INSTALLATION AND OPERATION MANUAL Rev 04 19 ...

Страница 2: ...tic and manual operation modes selectable via 3 positional key lock allow the operators to choose the extinguishing process control The FP9000E conventional panel is designed for extinguishing in one zone and can operate with solenoids pressostats and other kind of actuators Each fire line can be connected to 32 detectors Through the display and keyboard can be programmed and adjusted over 50 func...

Страница 3: ... entering Fire mode 1 2 or 3 programmable Verification and regestrating fault in a earth conductor yes selectively programmable Supervised balanced inputs Manual Release The Manual Release input is normally open 1 Hold The Hold input can be configured input is normally open input is normally closed 1 selectively programmable Low Press The Low Press input can be configured input is normally open in...

Страница 4: ...tored outputs OC Open Collector type OK1 Disabled mode selected Low Pressure event Electrical characteristics 30mA OK2 Manual mode selected Electrical characteristics 30mA OK3 Low Pressure event Electrical characteristics 30mA OK4 Hold Activation event Electrical characteristics 30mA Independent relay output in case of failure Quantity 1 Type potentional free switching NC NO Electrical characteris...

Страница 5: ...ector and automatic reset Light and textual indication for Fire Activated Extinguish Fault Disable and Test mode Ability to delay controllable and general outputs for extinguishing for a period of 1 to 60 seconds after the registration of state Activated Built in sounder in case of fire monotonal continuous with the possibility of exclusion Test mode of each fire alarm lines Ability to Disable eac...

Страница 6: ...a steady yellow light will light up OUTS yellow Illuminates with steady yellow light at short or interruption of output devices power supply line DEL OUTS yellow Continuous yellow light at preset delay of connected outputs BUZZER SILENCE red Indicator to the button BUZZER SILENCE in suppressing local buzzer a steady red light will light up SOUND SILENCE red Indicator to the button SOUND SILENCE wh...

Страница 7: ...ment condition Information and management Levels 1 and 2 Displaying the next element onto the display Moving of the cursor Modification of the selected parameter Fire Levels 1 and 2 Displaying the previous text messege for Fire onto the display Information and management Level 1 and 2 Displaying the previous element onto the display Modification of the selected parameter Options Level 3 Fire Level...

Страница 8: ...h conductor On programmable Supervised balanced inputs Manual Release The Manual Release input is normally open Hold The Hold input is normally open programmable Low Press The Low Press input is normally open programmable Mode Select The Mode Select input is normally open On Off Exting Enable Disable Extinguishing The On Off Exting input is normally open Potential outputs EXT Extinguishing EN 1209...

Страница 9: ...a signal to the control panel via call point for starting the extinguishing in the protected area More than one call point can be connected to this line Hold Supervised balanced input This input is used for sending a signal to the control panel via call point or a pressure switch for holding delaying the extinguishing in the protected area The active state of the input NC Normal closed or NO Norma...

Страница 10: ... key selector switch is set to MANUAL operation mode OK3 Open collector output The output changes its state in case of Low pressure activation event OK4 Open collector output The output changes its state in case of Hold activation event 5 3 Connecting Fire detectors Line 1 and Line 2 are extinguishing zones Use 2 wire cross zoning connection of the detectors in the flooding area The extinguishing ...

Страница 11: ...checks When setting up with 1 check panel enters Fire condition immediately after activation of the Fire alarm This setting is recommended for lines with MCP When setting up 2 alarms After the first activation the panel resets the line for 3 seconds and awaits a second response in the next 60 seconds If there is a response in this period the panel enters Fire condition This setting is recommended ...

Страница 12: ...d when S 2 output is activated Fire Stage 2 operation mode is active S 2 circuit output is activated at Fire Alarm Stage 2 operation mode when Zone 1 and Zone 2 are activated The button Manual Release is manually pressed 5 5 Connecting to the Supervised Inputs The supervised inputs Manual Release Hold Mode Select ON OFF Extinguishing and Low Press are used for controlling the operation of the pane...

Страница 13: ...ty with the total resistance in the circuit lower than 10Ω It is mandatory to connect the main power supply cable to the middle input of the fire panel terminal The cable should be double insulated and section not less than 0 5 mm2 for power cables and 1 5 mm2 for the safety ground wire The other end of the feeding cable is connected to the mains using a junction box The mains power supply of the ...

Страница 14: ...rruption Example The factory settings are with current interruption 4 mA when a measurement of current in standby condition is done line is recommended to be from 6 mA to 9 mA If using linear non standard and other Fire alarms detectors it is necessary to adjust the currents break and Fire so that the panel can be able to recognize them correctly Set the accession of exits and the respective delay...

Страница 15: ...nformation on the display The selection happens from the second menu of the main menu Access Level After entering the menu with button Enter and the corresponding buttons up and down choose the level Confirm again with Enter The selected level in Security Duty mode is displayed in the upper right corner of the display Access level 3 In Level 3 is reached by entering a password and opening the fron...

Страница 16: ... Stage 1 operation mode activated by Zone 1 and a second fire alarm from Zone 2 is generated Fire Alarm Stage 1 operation mode activated by Zone 2 and a second fire alarm from Zone 1 is generated Fire Alarm Stage 1 operation mode activated by Zone 3 and fire alarms from Zone 1 AND Zone 2 are generated The panel is in normal operation mode and the MANUAL RELEASE button on the front panel is pressed...

Страница 17: ... fast flashing Upon fault in a controllable output indicator OUTS lights up with flashing yellow light Upon fault in mains supply indicator POWER FAULT lights up in continuous yellow light Fault in the local network or the transmission device indicator COMUN lights up with a steady yellow light If the sound signal is suppressed by button BUZZER SILENCE LED indicator lights up a constant red light ...

Страница 18: ...anges are in effect Upon registration of Fire event in the line sound and light indications and associated controllable and relay output for failure are not activated ie the panel does not enter Fault Condition Events in the line are not saved in the energy independent achive The line is reset shuts off its power supply for time 3sec automatically every 60s LED indication light up indicators TEST ...

Страница 19: ...input Hold Setup input Low pressure Input factory settings menu Change the password to access the setup menu Delete archive When working with menus to have the following characteristics When working with menus use the four active buttons for information and management see Controlsfor management and indication If you enter into the menu s structure and has no activity for more than 30 seconds it au...

Страница 20: ... startup has been done by authorized persons The requirements for operation conditioned in this instruction were met Defects are not caused by natural phenomena and accidents of thr plug socket DMTech wishes you splendid work For any questions may contact the company s technical staff DMTech by email e mail office dm teh com ...

Отзывы: