Instructions for installation, setup and operation - FP9000E
Page
4
of
20
Electrical characteristics
24 VDC/ 0,5A
EXT (Extinguishing, EN 12094-1) – Monitored:
Type
potentional relay
Electrical characteristics
24 VDC/1.5A 15min
,
24 VDC/3A 100ms
Adjustable time triggering the output of 5 to
900 seconds.
programmable
Relay outputs:
1 Stage Relay (FIRE STAGE 1) – Non-monitored:
Type
potentional-free
NO
Electrical characteristics
3А/125V AC,
3A/30V DC
2 Stage Relay (FIRE STAGE 2) – Non-monitored:
Type
potentional-free
NO
Electrical characteristics
3А/125V AC,
3A/30V DC
Non-monitored outputs, OC (Open Collector) type:
OK1 (Disabled mode selected Low Pressure event)):
Electrical characteristics
30mA
OK2 (Manual mode selected):
Electrical characteristics
30mA
OK3 (Low Pressure event):
Electrical characteristics
30mA
OK4 (Hold Activation event):
Electrical characteristics
30mA
Independent relay output in case of failure:
Quantity
1
Type
potentional-free,
switching
NC / NO
Electrical characteristics
3А/125V AC,
3A/30V DC
Independent relay output in case of fire alarm:
Quantity
1
Type
switching
NC / NO
Electrical characteristics
3А/125V AC,
3A/30V DC
POWER SUPPLY
Mains power
Voltage
(110-252)V AC
Frequency
50/60 Hz
Maximum power to mains power
55W / AC
Consumption from the main power supply in
standby mode:
15 mA / 230V AC
Battery power
Battery quantity
2