Instructions for installation, setup and operation - FP9000E

 

 

Page 

5

 of 

20

 

 

 

Type of the battery 

Lead, gel 

 

 

Battery rated voltage  

12V DC 

 

 

Reted power C20 

5 (4.5)Ah 

 

 

Internal resistance of the accumulator battery  

Ri: < 0.3Ω 

 

 

Charger voltage 

27,4 VDC 

temperature 
compensated 

Consumption of battery power  

 

standby mode 

< 35 mA to 24 VDC   

Time needed in security mode when mains power supply is down with battery: 

 

12V/ 5Ah 

90h 

 

Executive devicess powering 

 

Voltage 

(19-27)V DC 

 

 

Maximal current (including the controllable 
outputs current) 

2А 

 

Fuses 

 

Mains power 230V AC 

4,0 A fusible 

 

 

Battery power 

6,3 А fusible 

 

 

Powering external devices 

1,85 А automatic 

 

 

Controllable outputs 

1,1 А automatic 

 

Functional characteristics 

 

Control of the lines, supervised balanced inputs and controllable outputs for fault 
conditions (short circuit and interruption) and automatic reset;

 

 

Control of the lines for down fire detector and automatic reset; 

 

Light and textual indication for Fire, Activated, Extinguish, Fault, Disable and Test mode; 

 

Ability to delay controllable and general outputs for extinguishing for a period of 1 to 60 
seconds after the registration of state Activated; 

 

Built-in sounder in case of fire – monotonal, continuous with the possibility of exclusion; 

 

Test mode of each (fire alarm) lines; 

 

Ability to Disable each of the fire alarm lines; 

 

Ability to Disable controllable output S 1 (Sounder 1); 

 

LCD display, 2×16 characters and keyboard, for control and panel indication; 

 

Energy independent archive of the events, recorded by the panel, consisting of type, date 
and time of the event - to 1900 events; 

 

Choice of language for text information display;

 

 

A set of test modes and options for adjustment of lines, outputs and panel. 

 

Over all size    

 

 

310х240х90  mm 

 

 

Weight without batteries 

1,3 kg 

 

Safety degree 

IP30/  EN 60529 

 

Operation temperature: 

minus 5ºС up to +40ºC 

 

Relative humidity 

up to 95%  

 

Storage temperature 

minus 10ºС up to +60ºC 

 

The panel meets standarts: 

 

EN12094:2003 

 

EN 54-2:1997 

 

EN 54-2:1997/A1:2006 

Содержание FP9000E

Страница 1: ...com web www dm teh com Address Pleven Bulgaria 5800 16 Nikolay Haytov Str DMTech Ltd Pleven Bulgaria 16 Nikolay Haytov Str Tel 359 64 801 597 e mail office dm teh com Page 1 of 19 DMTech Ltd Pleven Extinguishing Control Panel FP9000E INSTALLATION AND OPERATION MANUAL Rev 04 19 ...

Страница 2: ...tic and manual operation modes selectable via 3 positional key lock allow the operators to choose the extinguishing process control The FP9000E conventional panel is designed for extinguishing in one zone and can operate with solenoids pressostats and other kind of actuators Each fire line can be connected to 32 detectors Through the display and keyboard can be programmed and adjusted over 50 func...

Страница 3: ... entering Fire mode 1 2 or 3 programmable Verification and regestrating fault in a earth conductor yes selectively programmable Supervised balanced inputs Manual Release The Manual Release input is normally open 1 Hold The Hold input can be configured input is normally open input is normally closed 1 selectively programmable Low Press The Low Press input can be configured input is normally open in...

Страница 4: ...tored outputs OC Open Collector type OK1 Disabled mode selected Low Pressure event Electrical characteristics 30mA OK2 Manual mode selected Electrical characteristics 30mA OK3 Low Pressure event Electrical characteristics 30mA OK4 Hold Activation event Electrical characteristics 30mA Independent relay output in case of failure Quantity 1 Type potentional free switching NC NO Electrical characteris...

Страница 5: ...ector and automatic reset Light and textual indication for Fire Activated Extinguish Fault Disable and Test mode Ability to delay controllable and general outputs for extinguishing for a period of 1 to 60 seconds after the registration of state Activated Built in sounder in case of fire monotonal continuous with the possibility of exclusion Test mode of each fire alarm lines Ability to Disable eac...

Страница 6: ...a steady yellow light will light up OUTS yellow Illuminates with steady yellow light at short or interruption of output devices power supply line DEL OUTS yellow Continuous yellow light at preset delay of connected outputs BUZZER SILENCE red Indicator to the button BUZZER SILENCE in suppressing local buzzer a steady red light will light up SOUND SILENCE red Indicator to the button SOUND SILENCE wh...

Страница 7: ...ment condition Information and management Levels 1 and 2 Displaying the next element onto the display Moving of the cursor Modification of the selected parameter Fire Levels 1 and 2 Displaying the previous text messege for Fire onto the display Information and management Level 1 and 2 Displaying the previous element onto the display Modification of the selected parameter Options Level 3 Fire Level...

Страница 8: ...h conductor On programmable Supervised balanced inputs Manual Release The Manual Release input is normally open Hold The Hold input is normally open programmable Low Press The Low Press input is normally open programmable Mode Select The Mode Select input is normally open On Off Exting Enable Disable Extinguishing The On Off Exting input is normally open Potential outputs EXT Extinguishing EN 1209...

Страница 9: ...a signal to the control panel via call point for starting the extinguishing in the protected area More than one call point can be connected to this line Hold Supervised balanced input This input is used for sending a signal to the control panel via call point or a pressure switch for holding delaying the extinguishing in the protected area The active state of the input NC Normal closed or NO Norma...

Страница 10: ... key selector switch is set to MANUAL operation mode OK3 Open collector output The output changes its state in case of Low pressure activation event OK4 Open collector output The output changes its state in case of Hold activation event 5 3 Connecting Fire detectors Line 1 and Line 2 are extinguishing zones Use 2 wire cross zoning connection of the detectors in the flooding area The extinguishing ...

Страница 11: ...checks When setting up with 1 check panel enters Fire condition immediately after activation of the Fire alarm This setting is recommended for lines with MCP When setting up 2 alarms After the first activation the panel resets the line for 3 seconds and awaits a second response in the next 60 seconds If there is a response in this period the panel enters Fire condition This setting is recommended ...

Страница 12: ...d when S 2 output is activated Fire Stage 2 operation mode is active S 2 circuit output is activated at Fire Alarm Stage 2 operation mode when Zone 1 and Zone 2 are activated The button Manual Release is manually pressed 5 5 Connecting to the Supervised Inputs The supervised inputs Manual Release Hold Mode Select ON OFF Extinguishing and Low Press are used for controlling the operation of the pane...

Страница 13: ...ty with the total resistance in the circuit lower than 10Ω It is mandatory to connect the main power supply cable to the middle input of the fire panel terminal The cable should be double insulated and section not less than 0 5 mm2 for power cables and 1 5 mm2 for the safety ground wire The other end of the feeding cable is connected to the mains using a junction box The mains power supply of the ...

Страница 14: ...rruption Example The factory settings are with current interruption 4 mA when a measurement of current in standby condition is done line is recommended to be from 6 mA to 9 mA If using linear non standard and other Fire alarms detectors it is necessary to adjust the currents break and Fire so that the panel can be able to recognize them correctly Set the accession of exits and the respective delay...

Страница 15: ...nformation on the display The selection happens from the second menu of the main menu Access Level After entering the menu with button Enter and the corresponding buttons up and down choose the level Confirm again with Enter The selected level in Security Duty mode is displayed in the upper right corner of the display Access level 3 In Level 3 is reached by entering a password and opening the fron...

Страница 16: ... Stage 1 operation mode activated by Zone 1 and a second fire alarm from Zone 2 is generated Fire Alarm Stage 1 operation mode activated by Zone 2 and a second fire alarm from Zone 1 is generated Fire Alarm Stage 1 operation mode activated by Zone 3 and fire alarms from Zone 1 AND Zone 2 are generated The panel is in normal operation mode and the MANUAL RELEASE button on the front panel is pressed...

Страница 17: ... fast flashing Upon fault in a controllable output indicator OUTS lights up with flashing yellow light Upon fault in mains supply indicator POWER FAULT lights up in continuous yellow light Fault in the local network or the transmission device indicator COMUN lights up with a steady yellow light If the sound signal is suppressed by button BUZZER SILENCE LED indicator lights up a constant red light ...

Страница 18: ...anges are in effect Upon registration of Fire event in the line sound and light indications and associated controllable and relay output for failure are not activated ie the panel does not enter Fault Condition Events in the line are not saved in the energy independent achive The line is reset shuts off its power supply for time 3sec automatically every 60s LED indication light up indicators TEST ...

Страница 19: ...input Hold Setup input Low pressure Input factory settings menu Change the password to access the setup menu Delete archive When working with menus to have the following characteristics When working with menus use the four active buttons for information and management see Controlsfor management and indication If you enter into the menu s structure and has no activity for more than 30 seconds it au...

Страница 20: ... startup has been done by authorized persons The requirements for operation conditioned in this instruction were met Defects are not caused by natural phenomena and accidents of thr plug socket DMTech wishes you splendid work For any questions may contact the company s technical staff DMTech by email e mail office dm teh com ...

Отзывы: