Instructions for installation, setup and operation - FP9000E
Page
5
of
20
Type of the battery
Lead, gel
Battery rated voltage
12V DC
Reted power C20
5 (4.5)Ah
Internal resistance of the accumulator battery
Ri: < 0.3Ω
Charger voltage
27,4 VDC
temperature
compensated
Consumption of battery power
standby mode
< 35 mA to 24 VDC
Time needed in security mode when mains power supply is down with battery:
12V/ 5Ah
90h
Executive devicess powering
Voltage
(19-27)V DC
Maximal current (including the controllable
outputs current)
2А
Fuses
Mains power 230V AC
4,0 A fusible
Battery power
6,3 А fusible
Powering external devices
1,85 А automatic
Controllable outputs
1,1 А automatic
Functional characteristics
Control of the lines, supervised balanced inputs and controllable outputs for fault
conditions (short circuit and interruption) and automatic reset;
Control of the lines for down fire detector and automatic reset;
Light and textual indication for Fire, Activated, Extinguish, Fault, Disable and Test mode;
Ability to delay controllable and general outputs for extinguishing for a period of 1 to 60
seconds after the registration of state Activated;
Built-in sounder in case of fire – monotonal, continuous with the possibility of exclusion;
Test mode of each (fire alarm) lines;
Ability to Disable each of the fire alarm lines;
Ability to Disable controllable output S 1 (Sounder 1);
LCD display, 2×16 characters and keyboard, for control and panel indication;
Energy independent archive of the events, recorded by the panel, consisting of type, date
and time of the event - to 1900 events;
Choice of language for text information display;
A set of test modes and options for adjustment of lines, outputs and panel.
Over all size
310х240х90 mm
Weight without batteries
1,3 kg
Safety degree
IP30/ EN 60529
Operation temperature:
minus 5ºС up to +40ºC
Relative humidity
up to 95%
Storage temperature
minus 10ºС up to +60ºC
The panel meets standarts:
EN12094:2003
EN 54-2:1997
EN 54-2:1997/A1:2006