Instructions for installation, setup and operation - FP9000E
Page
11
of
20
Fig.2
One line can allow the installation of up to 32 Fire detectors generally, regardless of their type.
To the unused lines, directly to the terminals mount the final element "EOL", otherwise the lines
will be able in Fault condition.
FIRE LINES - Parameters programming and setting.
For each Fire line individually, through the menus of the panel, there is an opportunity to set the
following parameters:
Current interruption
It can change the current interruption from 1 mA to 12 mA. The factory setting is 4 mA. The
feature gives flexibility in installation of the panel, both existing installations and new, with
sensors and final elements of any type.
Current Fire
The limit current of Fire condition can be varied from 12 mA to 99 mA. The factory setting is 16
mA. The function enables the use of conventional Fire alarms detectors of any type and
manufacturer.
Number of checks
The setting provides a choice of 1, 2 or 3 checks before the line to enter the condition "Fire." The
default setting is for 2 checks.
-
When setting up with 1 check, panel enters Fire condition immediately after activation of
the Fire alarm. This setting is recommended for lines with MCP.
-
When setting up 2 alarms. After the first activation, the panel resets the line for 3 seconds
and awaits a second response in the next 60 seconds. If there is a response in this period
the panel enters Fire condition.This setting is recommended for lines with automatic Fire
detectors the aim of ignoring false alarms.
-
When setting up to 3 alarms. After the first activation, the panel resets the line for 3
seconds and awaits a second response in the next 60 seconds. If there is a response in this
period, the panel again resets the line for 3 seconds and awaits for the third activation in
the next 60 seconds, if any, the panel enters Fire condition. This setting is also
recommended for lines with automatic fire detector for greater security when the Warning
and extinguishing.
Inclusion of relay outputs in fire condition in the line.
An additional relay module M9000R with 2/4/6/8 relays can be added to the panel, which can be
configured in case of a fire alarm to the corresponding line.
5.4 Sounders Circuits Wiring
To every monitored output Sn could be connected several sounders – Fig.3. The maximum number of