Instructions for installation, setup and operation - FP9000E
Page
6
of
20
EN 54-2:1997/AC:1999
EN 54-4:1997
EN 54-4:1997/A1:2002
EN 54-4:1997/A2:2006
EN 54-4:1997AC:1999
EN 50130-4:2011
EN 55022:2006/А1:2007
EN 60950-1:2006/А11:2009
3. CONTROLS AND INDICATION
LED indicators
Indicators
Function
“POWER”
green
Constant green light
“ACTIVATED”
red
Blinking –Fire Stage 1 / Fire EN54-2
Lights ON - Fire Stage 2 / Activated ЕN12094
“RELEASED”
red
Lights ON in case the release occurred.
/ Released ЕN12094
“FAULT”
yellow
A common failure indicator. Upon failure of any type a yellow
light will start flashing
“SYS FAULT”
yellow
A system failure due to stoppage of the CPU. A constant yellow
light will light up. Needs to be repaired at an authorized service.
“POWER FAULT”
yellow
In case of fault or loss of an AC or battery power supply a steady
yellow light will light up.
“TEST”
yellow
When in line test condition a constant yellow light will light up.
“DISABLE”
yellow
When in Disabled component / line or controllable output / a
steady yellow light will light up.
“OUTS”
yellow
Illuminates with steady yellow light at short or interruption of
output devices power supply line
“DEL OUTS”
yellow
Continuous yellow light at preset delay of connected outputs
“BUZZER
SILENCE”
red
Indicator to the button "BUZZER SILENCE", in suppressing local
buzzer, a steady red light will light up.
“SOUND
SILENCE”
red
Indicator to the button "SOUND SILENCE", when suppressing
Fire outputs, a steady red light will light up.
“MANUAL”
yellow
The extinguishing process is manually operated only.
“DISABLE EXT”
yellow
The extinguishing process is disabled
“HOLD”
yellow
Lights ON in case of HOLD input has been operated
“AUTO”
yellow
The extinguishing process is automatic. In case of Fire Alarm
Stage 2 the extinguishing process will run automatically or can be
manually operated with pressing MANUAL RELEASE button on
the front panel.
“PRESOSTAT”
yellow
Lights ON in case of LOW PRESSURE input has been operated.
“FLOW
CONTROL”
yellow
Lights ON in case of FLOW CONTROL input has been operated
“ELEKTRO
VALVE”
yellow
Lights ON in case of the extinguishing output has been operated
“1 2 3”
red
Individual indicators for Fire. Lights on permanently in case of fire
alarm in line.