Instructions for installation, setup and operation - FP9000E
Page
8
of
20
4. DEFAULT PARAMETERS
The fire panel provides users with default parameters, described in the table below. These parameters are
saved and recorded from menu "Default par.".
Fire Lines
Current thresholds in the Fire lines:
Interuption
from 4 mA
Duty mode
from 5 to 16 mA
Fire
from 17 to 99 mA
Short cicuit
> 100 mA
Lines’ functional characteristics:
Verification quantity before entering in fire
state:
2
programmable
Verification and regestrating fault in a earth
conductor
On
programmable
Supervised balanced inputs
Manual Release:
The “Manual Release” input is:
normally open.
Hold:
The “Hold” input is:
normally open
programmable
Low Press.:
The “Low Press.” input is:
normally open
programmable
Mode Select:
The “Mode Select” input is:
normally open
On/Off Exting (Enable/Disable Extinguishing):
The “On/Off Exting” input is:
normally open
Potential outputs
EXT (Extinguishing, EN 12094-1):
Time triggering the output:
10
seconds
programmable
Functional characteristics
Time for evacuation:
60
seconds
programmable
5. PANEL INSTALATION AND SETUP
5.1 Panel assembly.
Unpack the panel;
Mount the dowels at the appointed place for fixing the panel;
Attach the panel to the dowels through the three holes on the chassis