The extinguishing panel is in normal operation mode (stand-by) when only the LED “POWER ON” on
the front power is lighting on in green. The internal buzzer and all other status LEDs are off. The key for
selection of the extinguishing mode is set to Automatic, Manual or Disabled position.
8.2. Fire Alarm Stage 1 /Fire EN54-2/
The extinguishing panel goes to Fire Alarm Stage 1 operation mode when a fire alarm is generated from a
detector or call point in only one of the fire zones – Zone 1, Zone 2 or Zone 3.
During Fire Alarm Stage 1 operation mode are activated.
- The sounder output S1 and the internal buzzer.
- The Fire Stage 1 Relay output.
- The FIRE LED (red) of the Zone detected fire and ACTIVATED LED is blinking in red on the front
panel.
The User can stop the signalization of the internal buzzer by pressing the SILENCE BUZZER button.
The S1 output can be suppressed by pressing the SILENCE SOUNDERS button – the yellow LED lights
on.
The extinguishing process can be manually started by pressing the MANUAL RELEASE button on the
front panel if the mode selector for the extinguishing is set to MANUAL or AUTOMATIC position
.
8.3. Fire Alarm Stage 2 /Aitivated EN 12094/
The extinguishing panel goes to Fire Alarm Stage 2 if one of the following events are following in
sequence:
- Fire Alarm Stage 1 operation mode activated by Zone 1 and a second fire alarm from Zone 2 is
generated.
- Fire Alarm Stage 1 operation mode activated by Zone 2 and a second fire alarm from Zone 1 is
generated.
- Fire Alarm Stage 1 operation mode activated by Zone 3 and fire alarms from Zone 1 AND Zone 2 are
generated.
- The panel is in normal operation mode and the MANUAL RELEASE button on the front panel is
pressed (the mode selector for the extinguishing is set to MANUAL or AUTOMATIC position).
During Fire Alarm Stage 2 operation mode are activated:
- The sounder output S2 and the internal buzzer.
- The Fire Stage 2 Relay output.
- The FIRE LED (red) of the Zones detected fire and the ACTIVATED LED lights on in red on the front
panel.
- The Evacuation time starts running counting down the time left to starting the extinguishing on the site.
The ACTIVATED LED lights on in red.
- The extinguishing devices are activated – the RELEASED LED lights on in red.
The S2 output cannot be silenced
. The user can only stops the signalization of the internal buzzer by
pressing the SILENCE BUZZER button.
Pressing of HOLD button (connected to supervised input HOLD on the main PCB) will reset the
evacuation time.
8.4. Extinguishing
The extinguishing is a process for releasing of extinguishing agents via special automatic devices in case
of fire alarm in the protected premises.
The extinguishing process can be started automatically at any time with pressing the MANUAL
RELEASE button on the front panel when the mode selector for the extinguishing is set to MANUAL or
AUTOMATIC position.