SECTION 2
DDFP
Page 11
PREVENTIVE MAINTENANCE SCHEDULE
Inspection Interval
6 Months
1 Year
2 Year
Weekly
Item
1. Run Engine
(per NFPA 20 Specifications)
X
2. General Inspection
X
3. Lubricating Oil
X
R
4. Fuel Tank
X
5. Fuel Lines
X
6. Cooling System
X
R
7. Battery
X
C
8. Air Cleaner - Dry Type (-03AN & -04AN)
X
R
R
- Oil Gauze (All Other Models)
X
C
R
9. Drive Belts
X
10. Speed Control
X
11. Fuel & Lube Oil Filters
R
12. Exhaust System
X
X
13. Battery Charging Alternator
X
14. Manual Contractors
X
15. Operating Gauges
X
16. Crankcase Vent System
X
17. Heat Exchanger Electrode
X
18. Governor Run-Stop Mechanism
X
19. Jacket Water Heater
X
20. Wiring System
X
21. Coolant Hose Inspection
X
R
See Parts Information Section 6 for Lubricating Oil And Coolant Analysis' Kits
IMPORTANT:
Set AEC to "of f" while servicing engine.
Before turning the AEC to the "off" position, check with the
maintenance and security supervisors to v erify that all de-
partments concerned will be alerted of the temporary inter-
ruption of their f ire protection equipment for normal main-
tenance or testing. Also, alert the local fire department in the
event that the AEC is connected by silent alarm to head-
quarters. When servicing is complete,return AEC selector to
"Automatic" position and the manual operating le
ver to
"auto - off" position.
X Check
R Replace
C Clean
Содержание DDFP Series
Страница 13: ...DDFP SECTION 2 Front View V 71 Page 9 A Front View I 71 Right Side View I 71 Right Side View 6V 71 ...
Страница 14: ...Page 9 B SECTION 2 DDFP Front View 12V 92 Left Side View 12V 92 Front View V 92 Right Side View V 92 ...
Страница 22: ...SECTION 3 2 DDFP AIR FILTER SERVICE INSTRUCTIONS Figure 1 Air Filter Service Instructions Page 17 ...
Страница 42: ...SECTION 3 5 DDFP Page 37 Fig 13 DC Wiring Diagram Engines With Mechanical Guages ...
Страница 43: ...DDFP Fig 14 DC Wiring Diagram Engines With Electrical Guages Page 38 SECTION 3 5 ...
Страница 44: ...SECTION 3 5 DDFP Page 39 Fig 15 AC Wiring Diagram ...