CVIR II
text
Comments
Imax
The cycle was aborted because the maximum tool current is reached.
This over consumption may also be due to short-circuit, a cable fault, a resolver fault or an offset
resolver fault.
Reading
eepROM
Indicates an access error to the tool's EEPROM memory:
writing
When one of the following operations is wrongly carried out:
● Log out / Data writing / Data re-reading / Data recorded comparison.
Reading
When switched on, the CVIR II carries out a complete memory check.
● CRC of the parameters: TOOL PROGRAMMING ERROR.
● Parameter version: TOOL VERSION ERROR.
● Parameter changing: CHANGE OF TOOL.
● Counter CRC: TOOL PROGRAMMING ERROR.
● Tool cycle CRC: TOOL PROGRAMMING ERROR.
● Cycle 0 CRC: TOOL PROGRAMMING ERROR.
● Torque/Current table CRC: TOOL PROGRAMMING ERROR.
● Controller/Tool compatibility: CURRENT TRANSDUCER INCOMPATIBLE WITH TOOL.
Resolver
Position change or non zero speed detected when the motor start is not activated.
Only checked in Test mode.
temperature
Indicates power components (IGBT) over temperature.
The temperature is measured on the power components' cooling radiator.
When the temperature exceeds 75 °C, the error is activated and remains until the temperature
returns below 70°C.
Note that this measure also starts the internal fan from 60°C onwards and stops the fan when the
temperature returns below 50°C.
Overall, it induces a Servo drive error, then a detailed Temperature error.
prg
The cycle was aborted due to a programming fault.
For example: the programmed torque is higher than the tool capacity.
ext
The cycle was aborted due to activation of the EXTERNAL STOP signal (if this option is selected
in the concerned phase).
tool
programming
Tool memory parameters are wrong.
tool version
The tool memory parameter version is not compatible with the CVIR II software version.
tool link
Tool memory parameter reading is impossible.
Current
transducer
incompatible
with tool
The connected tool is not compatible with the CVIR II model
(e.g.: ECA60 connected to CVIR II).
e01
The tool cannot run because the emergency stop is activated. Press “Enter” to get more
information.
e02
Controller busy (for example: down-loading or up-loading in progress).
e03
Batch of cycle complete (number of cycles OK) if the Lock on NCYOK box (lock after a batch of
cycle complete) in the STATION menu is activated.
e04
No cycle number validated on controller OR non-existing cycle number requested on the I/O port.
A question mark is displayed on the screen.
e05
Spindle is idle on a start signal.
No Spindle validation signal on the I/O port if the Spindle validation box is activated in the
STATION menu.
Tool will run only if the Spindle validation signal is activated on the I/O port.
e06
Start cycle arrives when the controller is not ready (may be due to a tool change, a Servo drive
error, etc. that has not been reset).
e07
Spindle is disabled after a Reject report.
If the Stop on bad report box in the STATION menu is activated, then the tool will be disabled.
To enable it, it is necessary to activate the Failure acknowledge input on the I/O port.
e09
CVINET FIFO is full.
The cycle can start but there is no free memory space left in the FIFO.
Problem with the Ethernet connection or configuration may be the cause.
e09
CVINET FIFO is full.
The cycle can not start because the Locking on when FIFO is full option is validated and there is
no free memory space left in the FIFO.
Problem with the Ethernet connection or configuration may be the cause.
e12
ToolsNet FIFO is full.
The cycle can start but there is no free memory space left in the FIFO.
Problem with the Ethernet connection or configuration may be the cause.