02/2014
37 / 72
6159933910
Issue no: 04
CVIR II
Outputs
Name
Factory
config.
Comments
pass through
p.thRu
When this value is set, I/O are devoted to PLC.
They are no longer read by the controller.
spindle ready
sp.RDy
This signal is at 1 when the tool is in working order.
In eRpht mode, if “Main direction” parameter is set to
“Main direction right” or “Main direction left”, tool direction
selector must be set to corresponding direction.
Run Reverse
enabled
ReVeRs
This signal switches to “1” when reverse mode is selected.
Otherwise it is at “0”
sequence OK
seQOK
This signal switches to “1” at the end of a successful sequence.
Otherwise it is at “0”
5.7.4.1 - CVIR II output, pLC input wiring
Below are shown the two wiring configurations available
for the relayed outputs of the CVIR II.
● The PLC 24V is connected to the CVIR II output
common. The PLC input do not receive external 24V.
+24V
0V
1
3
2
Legend
1 Controller output
2 pLC input
3 Common of the output relays
● By default, the PLC 24V is sent to the inputs of the
controller.
+24V
0V
0VE
1
3
2
Legend
1 Controller output
2 pLC input
3 Common of the output relays
All outputs are enabled at 1 and relayed in the controller
with a common point (4) for all outputs.
Features of the contacts: 1A / 30V / 30W max. DC on
resistive charge.