Issue no: 04
CVIR II
Inputs
Name
Factory
config.
Comments
pass through
p.thRu
When this value is set, I/O are devoted to PLC.
They are no longer read by the controller.
Reset Cycle
RstCy
This signal resets tightening report for last cycle in running sequence.
Running sequence is not aborted.
5.7.3.1 - pLC output, CVIR II input wiring
Two configurations are available.
● The CVIR II 24V is used as the Common of a PLC
relay board.
+24V
5.6kΩ
2.7kΩ
1
2
Legend
1 Controller input
2 pLC output
● By default, the PLC 24V is sent to the inputs of the
controller.
+24V PLC
5.6kΩ
2.7kΩ
0VE
0V
1
2
Legend
1 Controller input
2 pLC output
The inputs are type II as per standard CEI 1131-2
(24 V / 13 mA per input).