apply to installation of remote condensers.
•
Charge refrigerant blends, including R-410A and R-407C, with liquid only. Charging should be done
into the high side of the system whenever possible. Refer to section 5.5 for additional procedures
related to charging.
Note that the superheat should be stable and within 4 degrees of fluctuation. Minimum value
for superheat at compressor in all modes:
30.0 - 40.0
40.1 - 50.0
50.1 - 60.0
60.1 - 70.0
70.1 - 80.0
60.0 - 65.0
12
13
13
14
14
Superheat Minimum Values Chart Temp °F
65.1 - 70.0
13
14
14
15
15
70.1 - 75.0
14
15
15
15
16
80.1 - 85.0
15
16
18
18
19
75.1 - 80.0
15
15
16
16
18
85.1 - 90.0
16
18
18
19
20
Relative
Ai
r
Humidity (% RH)
Relative Air
Temperature °F
Figure 23 - Superheat Minimum Values Chart
3.4.1 Dehumidification / Cooling Mode
For Aura™ Products
In order to test the unit in dehumidification / cooling mode, the air temperature entering the DX
evaporator must be approximately 40°F or higher. If the condition entering the evaporator is lower,
the evaporator may accumulate significant amounts of frost and/or a suction pressure alarm may
occur.
If a low outdoor air temperature condition prevents the unit from running long enough to take data,
note this on a startup report and proceed to heat pump mode. During the first Preventative
Maintenance visit that is recommended during spring and fall, the service contractor should complete
the Dehumidification/Cooling Mode section of the startup report.
To perform start-up checks on the compressor, the supply air dewpoint set point should be lower
than the incoming dewpoint by at least 10°F. See the Controller IO Manual for instructions on setting
the dewpoint set point. Note the original setting. Once the set point is adjusted, switch the unit to
occupied
mode.
The compressor is controlled by a PID loop that will modulate the speed of the compressor to the
level necessary to achieve the desired dewpoint. It can take up to 15 minutes for the unit to reach
steady state during which time, the noise of the compressor will vary in frequency and intensity. This
is normal as the unit reaches steady state. During steady state operation, it is common for the
compressor to ramp up for short periods (about 30 seconds) in order to ensure proper oil return. This
will not substantially affect leaving air conditions and the unit will return to steady state within a few
minutes.