38
HP
0.5
1
1.5
2
3
5
7.5
10
15
20
25
30
40
1 Belt
3
7
12
Belt Deflection Force
2 Belts
7
12
3 Belts
12
2 Belts
5 - 6
8 - 9
New Belt Force (lbs.)
Used Belt Force (lbs.)
1 Belt
2 - 2.5
5 - 6
9 - 10
3 Belts
8 - 9
Figure 18 - Belt Deflection Force Table
•
Inspect the air filters and coils to assure they are clean. If necessary, clean the coils
and install new filters.
•
Check the field and factory piping for leaks. The internal piping may have been
damaged during shipping.
•
Purge any air, dirt, or debris from water lines (if used) to avoid clogging the internal
passages of optional heating coils or water side heat exchangers.
•
Check the drain pan and the condensate piping. Test the drain and prime the p-trap
by pouring water into the drain pan.
•
Verify that all service valves in the refrigeration lines are fully open.
3.2
Gas Heater Start-Up (Optional)
This optional furnace does not have a pilot. It is equipped with an igniter that automatically lights the burner.
Do not attempt to light the burner by hand. Check the following items before the initial start-up:
•
Check all wiring for loose connections and proper hookup. Leak test the gas piping
connections.
•
Check the rubber tubing to the inducer fan pressure switch to make sure it is pushed
firmly onto the pressure tap.
•
Indoor units only: Check all venting connections for tightness and to make sure there
is no blockage.
Desert Aire - QS/QV Manual