50
Note that duct airflow measurement equipment will be required to measure the amount
of airflow in each mode.
3.3.4.3 Recirculation Mode (TotalAire™)
Operate the unit in unoccupied mode of operation. Check to ensure that the
outside air damper indexes to the fully closed position, the return air damper
indexes to the fully open position, and the exhaust fan and enthalpy wheel turn
off. Adjust the blower speed such that the airflow meets specifications.
3.3.4.4 Mixed Air Mode (TotalAire™)
Operate the unit in occupied mode of operation. Initially the unit will index
the outdoor air damper fully open and the return air damper fully closed. Use
the maximum open position setting within the controller on the recirculation
damper to adjust the damper to a more open position in this mode. Check the
return air duct flow rate until the ratio of flows and the total flow is correct. Do
not adjust the blower speed at this time.
In cases where the return air static pressure is high, you may reach the full
open position of the outside air damper before the desired ratio is obtained.
Additionally, the airflow may be significantly higher than the specification in
this mode when this is the case. If this occurs, use the controller to adjust the
outdoor air damper maximum open position to limit the stroke of the actuator
to a less open position during this mode.
Adjust the return air damper to the close position and outdoor air damper to
the open position until the desired ratio and total specified airflow is achieved
in
occupied
mode.
Check the pressure drop across the enthalpy wheel according to the airflow
label on the side of the unit. Change the exhaust airflow, if necessary, by
adjusting the motor pulley or any balancing dampers in the field-installed
ductwork.
Verify exhaust air adjustments did not alter supply air operation. If so, repeat
above procedures until all airstreams are within specifications.
3.3.4.5 For Units with Systems Equipped with Demand Controlled
Ventilation Option (TotalAire™)
TotalAire™ units equipped with the CO
2
Control option include VFD’s for the
supply and exhaust as well as a recirculation damper. Pressure differential
across several components within the systems are measured. All of these
devices are connected to the unit controller which takes the inputs from these
pressure transducers and controls the fan speed accordingly.