44
Procedure:
1.
Check the condition of the air filters to assure that they are clean.
2.
Check for any obvious restrictions in the ductwork.
3.
Start the supply air blower.
4.
Drive the outdoor air damper open, start the supply air blower, and energize
the field-installed exhaust air blower by turning on the “occupied” switch.
Consult wiring diagram for location of occupied binary input jumper or use the
operating controller occupied scheduling feature.
5.
For TotalAire™ Units without Enthalpy Wheel:
Use a magnehelic or inclined
manometer to measure the air pressure drop across the reheat condenser
(ports #1 and #2). Compare this value to the value printed on the airflow label
on the side of the dehumidifier.
For TotalAire™ Units with Enthalpy Wheel:
Use a magnehelic or inclined
manometer to measure the air pressure drop across the upper and lower
sections of the enthalpy wheel. Compare these values to the values printed
on the airflow label on the side of the dehumidifier.
For Aura™ units:
Use a magnehelic or inclined manometer to measure the
air pressure drop across the reheat and dry evaporator. Compare this value
to the value printed on the airflow label on the side of the dehumidifier.
6.
Change the airflow, if necessary, by adjusting the motor pulley or any
balancing dampers in the field-installed ductwork.
Always measure the current draw of the blower motor after you make any changes to
the airflow quantity. If the motor draws more than its FLA rating but the total airflow is
still low, check the resistance of the ductwork. Verify that all grilles and dampers have
been opened and that there are no sudden turns or restrictions in the ductwork.
Refer to the mechanical equipment schedule or other indication from the building
designer for required flow rates.
3.3.2.2 Airflow Balancing for QV Dehumidifiers
The total airflow of a Desert Aire VerticalAire™ QV system can be checked by
measuring the static pressure drop across the reheat condenser and the dry
evaporator coil for models 4-15 tons. For QV units 20-30 tons, the airflow may
be checked by measuring the airflow across the reheat coil. The dehumidifier
features an adjustable blower sheave to simplify air balancing.
Desert Aire - QS/QV Manual