30
pressure immediately or at some future time. With the manual valve, on the combination
valve, positioned to prevent flow to the main burners, connect a manometer to the 1/8” pipe
outlet pressure tap on the valve. Open the valve and operate the heater to measure the
manifold gas pressure.
Note:
A manometer (fluid filled gauge) is recommended rather than
a spring type gauge due to the difficulty of maintaining calibration of a spring type gauge.
Normally adjustments should not be necessary to the factory present regulator. If adjustment
is necessary, set pressures to above settings by turning regulator screw IN (clockwise) to
increase pressure. Turn regulator screw OUT (counter clockwise) to decrease pressure.
Consult the valve manufacturer’s literature provided with the heater for more detailed
information.
2.10.3 Gas Heater Location
The following items must be considered when choosing the size and location of the
furnace. Note that dehumidifiers designed for outdoor use are already equipped with
combustion air intakes and venting means. Field-installed venting is only required on
indoor dehumidifiers.
•
All local codes and/or regulations take precedence over the instructions in this
manual and should be followed accordingly. In the absence of local codes,
installation must conform to these instructions, regulations of the National Fire
Protection Association, provisions of National Electrical Code (ANSI/NFPA70
latest edition), and the National Fuel Gas Code (ANSI Z223.1 latest edition).
•
Indoor units only:
The dehumidifier should be located as near the vent
terminal as practical to minimize the numbers of elbows and the length of any
horizontal run of connecting flue pipe which may be required.
•
Definitions of “combustible material” and “non-combustible material” as issued
by ANSI Z223.1 are as follows:
-
Combustible Material: Material made of or surfaced with wood,
compressed paper, plant fibers, plastics or other material that will
ignite and burn whether flameproof or not or whether plastered or not.
-
Non-Combustible Material: Material which will not ignite and burn;
such materials consisting entirely of steel, iron, brick, concrete, slate,
glass, plaster, or combination thereof.
•
Indoor units only:
The dehumidifier must be located on a level, dry surface in
an area which is free from and protected from excessive drafts or wind. It
must be installed so that the electrical components are protected from water.
If the area becomes wet or damp at times, the dehumidifier should be raised
above the floor using concrete blocks or steel dunnage.