29
•
LP Only:
Use the following line size chart to size the gas piping or tubing
between the LP tank and the second-stage regulator:
Section 1
Section 2
Total input
load (Btu/h)
on line
125,000
250,000
375,000
500,000
lf the length of line between regulators
(tank to building) is this long.
Use this size tubing to keep pr
essur
e dr
op below 2 lbs.
for maximum flow shown
.
Use this size tubing or pipe to keep
pr
essu
re
dr
op below 1/2” water
column for maximum flow shown.
Total input
load (Btu/h)
on line
75,000
125,000
187,500
250,000
375,000
500,000
lf the length of line between second-stage
regulator and furnace is this long.
25’
100’
1/2” O. D.
Copper
50’
75’
10’
5/8” O. D.
Copper
20’
30’
40’ 50’
3/4” Black
Pipe
1” Black Pipe
1” Black Pipe
3/4” Black Pipe
3/4” Black Pipe
3/4” Black Pipe
5/8” O. D. Copper
3/8” O. D. Copper
3/8” O. D. Copper
1/2” O. D. Copper
1/2” O. D. Copper
Figure 12- LP Gas Pipe Sizing Information
•
LP Only:
Seamless copper tubing may only be used with gases that are not
corrosive to it. See the note below to check with your LP gas supplier before
using copper. Seamless copper tubing must comply with standard type K or L
for seamless copper water tube, ASTM B 88; or seamless copper tube for air
conditioning field service, ASTM B 280.
•
LP Only:
Copper and brass tubing and fittings (except tin lined) shall not be
used if the gas contains more than a trace (0.3 grains per cubic ft.) of
hydrogen sulfide gas. Check with your gas supplier.
•
LP Only:
-
TotalAire™ units
- maximum supply pressure for liquefied petroleum
(LP) gas is 14” wc and minimum supply for purpose of input
adjustment
is
11”
wc.
-
Aura™ units
– maximum supply pressure for liquefied petroleum (LP)
gas is 13.5” wc and minimum supply for purpose of input adjustment
is
11”
wc.
Before attempting to measure or adjust high fire manifold gas pressure, the inlet (supply)
pressure must be within the specified range for the gas being both used when the heater is in
operation and on standby. Incorrect inlet pressure could cause excessive manifold gas
Desert Aire - QS/QV Manual
Содержание Aura QS
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire QS QV Manual ...
Страница 60: ...60 Desert Aire QS QV Manual ...
Страница 64: ...64 Desert Aire QS QV Manual ...
Страница 90: ...90 Additional Comments Desert Aire QS QV Manual ...
Страница 93: ...93 Desert Aire QS QV Manual ...