adjust the blower speed as required per blower adjustment procedure.
3.3.2.1 Aura™ and TotalAire™ Units
The total airflow of a TotalAire™ or Aura™ system can be checked by
measuring the static pressure drop across one or more of the following
components depending on the configuration: the reheat condenser, the
evaporator coil, or the enthalpy wheel. The dehumidifier features an
adjustable blower sheave to simplify air balancing. To measure airflow of
Aura™ units, measure the pressure drop across both the reheat condenser
and dry evaporator. Aura™ units have convenient ports located in the
electrical
system
compartment.
Figure 19- QS side view showing location of Air Balance Ports
Figure 20- Aura™ side view showing location of Air Balance Ports