Installation and Operating Manual for RPI M15A M20A Solar Inverter V1.0 2016-03-18
9 Settings
9.14 Ramp-up power
This setting should only be changed after consul-
tation with Delta customer service.
Overview
Using this function you can define the rise in active power for
occasions when the inverter disconnects from the grid as a result
of a voltage error or a frequency error.
After the error has disappeared, the active power is continuously
increased according to the preset rise rate.
Path to the menu item
Main Menu
>
Settings
>
Install Settings
>
Ramp-up Power
Setting options
Parameter
Description / Setting range
Ramp-up Power
Rise in active power in percent per minute.
Setting range:
0 ... 6000 %/min
Setting the ramp-up power
1.
If the default information is displayed, press the
EX IT
button
to open the main menu.
Alternatively, press the
EX IT
button repeatedly until the main
menu is displayed.
20
15
10
5
0
4
8
12
16
20
24
kW
2013.06.21
kWh
kWh
kg
2013.06.21
Hour
Peak Hours:
E-Day:
Day CO2 Saved:
Exit
Year
21. Jun 2013 09:30
Energy Log - Day
2.
Using the
and
buttons, select the
Settings
entry
and press the
ENT
button.
E-Today
Power Meter
Energy Log
Event Log
Inverter Information
Settings
Operation Data
21. Jun 2013 09:30
Menu
3.
Using the
and
buttons, select the
Install Set-
tings
entry and press the
ENT
button.
Personal Settings
Coefficients Settings
Install Settings
Active/Reactive Power Control
FRT
21. Jun 2013 09:30
Settings
4.
The function is protected with the password 5555.
Use the
and
buttons to set the individual digits.
Press the
ENT
button to confirm a digit.
3
3
3
3
ENT
21. Jun 2013 09:30