Installation and Operating Manual for RPI M15A M20A Solar Inverter V1.0 2016-03-18
9 Settings
9.26 Constant reactive power
The parameters are set according to the require-
ments of the selected country. A change to the
parameter settings may result in the approval be-
ing lost. This setting should only be changed after
consultation with Delta customer service.
Overview
You can set a constant reactive power with this function.
To change this setting you will need a special
password which you can obtain from Delta cus-
tomer service. You will find the contact data on
the last page of this document.
Path to the menu item
Main Menu
>
Settings
>
Active / Reactive Power Control
>
Reactive Power Control
>
Constant Reactive Power
Setting options
Parameter
Description / Setting range
Reactive Power
(Q/Sn)
Reactive power as a percentage of the
apparent power
0
ind 1 .. ind 63 %
kap 1 .. kap 63 %
Mode
Setting range:
ON
: The function is switched on.
OFF
: The function is switched off.
Calling up the menu item
1.
If the default information is displayed, press the
EX IT
button
to open the main menu.
Alternatively, press the
EX IT
button repeatedly until the main
menu is displayed.
20
15
10
5
0
4
8
12
16
20
24
kW
2013.06.21
kWh
kWh
kg
2013.06.21
Hour
Peak Hours:
E-Day:
Day CO2 Saved:
Exit
Year
21. Jun 2013 09:30
Energy Log - Day
2.
Using the
and
buttons, select the
Settings
entry
and press the
ENT
button.
E-Today
Power Meter
Energy Log
Event Log
Inverter Information
Settings
Operation Data
21. Jun 2013 09:30
Menu
3.
Using the
and
buttons, select the
Active/Reac-
tive Power Control
entry and press the
ENT
button.
Personal Settings
Coefficients Settings
Install Settings
Active/Reactive Power Control
FRT
21. Jun 2013 09:30
Settings