Installation and Operating Manual for RPI M15A M20A Solar Inverter V1.0 2016-03-18
9 Settings
5.
Using the
and
buttons, select the
Insulation
entry and press the
ENT
button.
[ 001 ]
Inverter ID
Insulation
RCMU
Country
Grid Settings
Reconnection Time
Ramp-up Power
UK G59/3 230V
[ ON ]
[ 20 ] S
[ 6000 ] %/m
21. Jun 2013 09:30
Install Settings
If you only want to set the insulation resistance,
you can go directly to Step 9.
6.
Using the
and
buttons, select the
Mode
entry and
press the
ENT
button.
550
[
] kohm
Resistance
Mode
ON
[
]
21. Jun 2013 09:30
Insulation
→ The present mode is highlighted and can be changed.
550
[
] kohm
Resistance
Mode
ON
[
]
21. Jun 2013 09:30
Insulation
7.
Use the
and
buttons to select a mode.
550
[
] kohm
Resistance
Mode
Negative Ground
[
]
21. Jun 2013 09:30
Insulation
8.
Press the
ENT
button to confirm.
þ
The new mode is set.
550
[
] kohm
Resistance
Mode
Negative Ground
[
]
21. Jun 2013 09:30
Insulation
9.
Using the
and
buttons, select the
Resistance
entry and press the
ENT
button.
550
[
] kohm
Resistance
Mode
ON
[
]
21. Jun 2013 09:30
Insulation
→ The value is highlighted and can be changed.