9 Settings
Installation and Operating Manual for RPI M15A M20A Solar Inverter V1.0 2016-03-18
112
Changing settings
The procedure is identical for all parameters.
1.
Using the
and
buttons, select a parameter and
press the
ENT
button.
1.00
[
] A
0.2
[
] s
Trip value
Trip time
Mode
ON
[
]
21. Jun 2013 09:30
DC Injection
→ The value is highlighted and can be changed.
1.00
[
]
A
0.2
[
] s
Trip value
Trip time
Mode
ON
[
]
21. Jun 2013 09:30
DC Injection
2.
Use the
and
buttons to select the value.
1.50
[
]
A
0.2
[
] s
Trip value
Trip time
Mode
ON
[
]
21. Jun 2013 09:30
DC Injection
3.
Press the
ENT
button to confirm.
→ The parameter is set.
1.50
[
] A
0.2
[
] s
Trip value
Trip time
Mode
ON
[
]
21. Jun 2013 09:30
DC Injection
Finalising the setting
1.
Press the
EX IT
button to finalise the setting.
þ
The function is set.
001
[
]
RCMU
Insulation
Inverter ID
DC Injection
Country
Return to Factory
Grid Settings
ON
[
]
Yes / No
UK G59/3 230V
[
]
21. Jun 2013 09:30
Install Settings