Installation and Operating Manual for RPI M15A M20A Solar Inverter V1.0 2016-03-18
9 Settings
9.24 Constant cos φ
This setting should only be changed after consul-
tation with Delta customer service.
Overview
With this function you can set a constant cos φ.
To change this setting you will need a special
password which you can obtain from Delta cus-
tomer service. You will find the contact data on
the last page of this document.
Path to the menu item
Main Menu
>
Settings
>
Active / Reactive Power Control
>
Reactive Power Control
>
Constant cos φ
Setting options
Parameter
Description / Setting range
cos φ
Constant cos φ
Setting range:
ind 0.80 ... ind 0.99
1.00
cap 0.80 ... cap 0.99
Mode
Setting range:
ON
: The function is switched on.
OFF
: The function is switched off.
Calling up the menu item
1.
If the default information is displayed, press the
EX IT
button
to open the main menu.
Alternatively, press the
EX IT
button repeatedly until the main
menu is displayed.
20
15
10
5
0
4
8
12
16
20
24
kW
2013.06.21
kWh
kWh
kg
2013.06.21
Hour
Peak Hours:
E-Day:
Day CO2 Saved:
Exit
Year
21. Jun 2013 09:30
Energy Log - Day
2.
Using the
and
buttons, select the
Settings
entry
and press the
ENT
button.
E-Today
Power Meter
Energy Log
Event Log
Inverter Information
Settings
Operation Data
21. Jun 2013 09:30
Menu
3.
Using the
and
buttons, select the
Active/Reac-
tive Power Control
entry and press the
ENT
button.
Personal Settings
Coefficients Settings
Install Settings
Active/Reactive Power Control
FRT
21. Jun 2013 09:30
Settings