User Manual
A9000
AC Power Source
98
│
www.deltaww.com
[SOURce:]PULSe:PERiod
Function
:
Set (query) total period of PULSE mode
Example
:
[SOURce:]PULSE:PERiod?
[SOURce:]PULSE:PERiod 600
Parameter
:
<NR1> Effective range
:
2 ~ 16000000 (unit: msec)
Parameter returns
:
<NR1>
[SOURce:]STEP:VOLTage:AC
Function
:
Set (query) start voltage for STEP mode.
Example
:
[SOURce:]STEP:VOLTage:AC?
[SOURce:]STEP:VOLTage:AC 150.5
Parameter
:
<NR2> effective range
:
0.0 ~ 150.0 (low level range),
0.0 ~ 300.0 (high level range)
Parameter returns
:
<NR2>
[SOURce:]STEP:DVOLtage:AC
Function
:
Set (query) voltage change for each step in STEP mode.
Example
:
[SOURce:]STEP:DVOLtage:AC?
[SOURce:]STEP:DVOLtage:AC 20.5
Parameter
:
<NR2> effective range
:
-150.0 ~ 150.0(unit
:
Volt)
Parameter returns
:
<NR2>
[SOURce:]STEP:FREQuency
Function
:
Set (query) start frequency for STEP mode
Example
:
[SOURce:]STEP:FREQuency?
[SOURce:]STEP:FREQuency 80.5
Parameter
:
<NR2> effective range
:
30.0 ~ 1000.0 (unit : Hz)
Parameter returns
:
<NR2>