Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-9
Group 3 Analog Input/Output Parameters
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQCPG
03-00
Analog Input 1 (AVI)
0: No function
1
○
○
○
○
○
03-01
Analog Input 2 (ACI)
1: Frequency command (torque limit under TQR control
mode)
0
○
○
○
○
○
03-02
Analog Input 3 (AUI) 2: torque command (torque limit under speed mode)
0
○
3: Torque compensation command
○
○
○
○
○
4: PID target value (refer to group 8)
○
○
○
○
5: PID feedback signal (refer to group 8)
○
○
○
○
6: P.T.C. thermistor input value
○
○
○
○
○
7: Positive torque limit
○
8: Negative torque limit
○
9: Regenerative torque limit
○
10: Positive/negative torque limit
○
11: PID feedback signal of tension
○
○
○
○
○
12: Line speed
○
○
○
○
○
13: Reel diameter
○
○
○
○
○
14: PID target value of tension (tension closed-loop)
○
○
○
○
○
15: Tension setting (tension open-loop)
○
16: Zero-speed tension
○
17: Tension taper
○
03-03
Analog Input Bias 1
(AVI)
-100.0~100.0%
0
○
○
○
○
○
03-04
Analog Input Bias 2
(ACI)
-100.0~100.0%
0
○
○
○
○
○
03-05
Analog Input Bias 3
(AUI)
-100.0~100.0%
0
○
○
○
○
○
03-06
Positive/negative Bias
Mode (AVI)
0
○
○
○
○
○
03-07
Positive/negative Bias
Mode (ACI)
0
○
○
○
○
○
03-08
Positive/negative Bias
Mode (AUI)
0: Zero bias
1: Lower than bias=bias
2: Greater than bias=bias
3: The absolute value of the bias voltage while serving
as the center
4: Serve bias as the center
0
○
○
○
○
○
03-09
Analog Input Gain 1
(AVI)
-500.0~500.0%
100.0
○
○
○
○
○
03-10
Analog Input Gain 2
(ACI )
-500.0~500.0%
100.0
○
○
○
○
○
03-11
Analog Input Gain 3
(AUI)
-500.0~500.0%
100.0
○
○
○
○
○
03-12
ACI/AVI2 Selection
0: ACI
1: AVI 2
0
○
○
○
○
○
03-13
Analog Input Delay
Time (AVI)
0.00~2.00 sec
0.01
○
○
○
○
○
03-14
Analog Input Delay
Time (ACI)
0.00~2.00 sec
0.01
○
○
○
○
○
03-15
Analog Input Delay
Time (AUI)
0.00~2.00 sec
0.01
○
○
○
○
○
03-16
Addition Function of
the Analog Input
0: Disable (AVI, ACI, AUI)
1: Enable
○
○
○
○
○
03-17
Loss of the ACI Signal 0: Disable
1: Continue operation at the last frequency
2: Decelerate to stop
3: Stop immediately and display E.F.
0
○
○
○
○
○
0: Output frequency (Hz)
0
○
○
○
○
○
03-18
Analog Output 1
1: Frequency command (Hz)
○
○
○
○
○
2: Motor speed (Hz)
○
○
○
○
○
03-21
Analog Output 2
3: Output current (rms)
○
○
○
○
○
4: Output voltage
○
○
○
○
○
03-24
Analog Output 3
5: DC Bus Voltage
○
○
○
○
○
6: Power factor
○
○
○
○
○
7: Power
○
○
○
○
○
8: Output torque
○
○
○
○
○
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Содержание VFD-VE
Страница 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...