Chapter 4 Parameters
|
4-118
Revision Dec. 2008, 04VE, SW V2.05
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Fault code
current Volt.
OL
SYS
FBK
EXI
CE
13: Low-voltage during constant
speed (Lvn)
●
14: Low-voltage at stop (LvS)
●
15: Phase loss (PHL)
●
16: IGBT over-heat (oH1)
●
17: Heat sink over-heat (oH2)(for
40HP above)
●
18: TH1: IGBT hardware failure
(tH1o)
●
19: TH2: Heat sink hardware
failure(tH2o)
●
20: Fan error signal output
●
21: over-load (oL) (when it exceeds
150% rated current, 1 min later it
will be overload)
●
22: Electronics thermal relay 1
(EoL1)
●
23: Electronics thermal relay 2
(EoL2)
●
24: Motor PTC overheat (oH3)
●
25: Fuse error (FuSE)
●
26: over-torque 1 (ot1)
●
27: over-torque 1 (ot2)
●
28: Reserved
29: Reserved
30: Memory write-in error (cF1)
●
31: Memory read-out error (cF2)
●
32: Isum current detection error
(cd0)
●
33: U-phase current detection error
(cd1)
●
34: V-phase current detection error
(cd2)
●