Chapter 2 Installation and Wiring
|
Revision Dec. 2008, 04VE, SW V2.05
2-13
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
+10V
Potentiometer Power Supply
+10VDC 20mA (variable resistor 3-5kohm)
MCM
Multi-function Output
Common (Photocoupler)
Max. 48VDC 50mA
MO1
Multi-function Output 1
(Photocoupler)
MO2
Multi-function Output 2
(Photocoupler)
Maximum 48VDC, 50mA
Refer to Pr.02-13 to Pr.02-14 for programming
MO1~MO2-DCM
MO1~MO2
MCM
Internal Circuit
Max: 48Vdc
50mA
AVI
Analog voltage Input
ACM
AVI
+10V
internal circuit
AVI circuit
Impedance: 200k
Ω
Resolution: 12
bits
Range:
0 ~ 10VDC = 0 ~ Max. Output
Frequency (Pr.01-00)
Set-up:
Pr.03-00 ~ Pr.03-02
ACI
Analog current Input
ACM
ACI
internal circuit
ACI circuit
Impedance: 250
Ω
Resolution: 12
bits
Range:
4 ~ 20mA/0~10V =
0 ~ Max. Output Frequency
(Pr.01-00)
Set-up:
Pr.03-00 ~ Pr.03-02
Jumper: ACI jumper, factory setting is
4-20mA
AUI
Auxiliary analog voltage input
ACM
AUI
+10
~
-10V
internal circuit
AUI circuit
Impedance: 200k
Ω
Resolution: 12
bits
Range:
-10 ~ +10VDC =
0 ~ Max. Output Frequency
(Pr.01-00)
Set-up:
Pr.03-00 ~ Pr.03-02
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Содержание VFD-VE
Страница 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...