Chapter 4 Parameters
|
4-4
Revision Dec. 2008, 04VE, SW V2.05
Group 1 Basic Parameters
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQCPG
01-00
Maximum Output
Frequency
50.00~600.00Hz 60.00/
50.00
○
○
○
○
○
01-01
1st Output Frequency
Setting 1
0.00~600.00Hz 60.00/
50.00
○
○
○
○
○
01-02
1st Output Voltage
Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
220.0
440.0
○
○
○
○
○
01-03
2nd Output Frequency
Setting 1
0.00~600.00Hz 0.50
○
○
01-04
2nd Output Voltage
Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
5.0
10.0
○
○
01-05
3rd Output Frequency
Setting 1
0.00~600.00Hz 0.50
○
○
01-06
3rd Output Voltage
Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
5.0
10.0
○
○
01-07
4th Output Frequency
Setting 1
0.00~600.00Hz 0.00
○
○
○
○
01-08
4th Output Voltage
Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
0.0
0.0
○
○
01-09
Start Frequency
0.00~600.00Hz 0.50
○
○
○
○
01-10
Output Frequency Upper
Limit
0.00~600.00Hz
600.00
○
○
○
○
01-11
Output Frequency Lower
Limit
0.00~600.00Hz
0.00
○
○
○
○
01-12 Accel Time 1
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-13 Decel Time 1
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-14 Accel Time 2
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-15 Decel Time 2
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-16 Accel Time 3
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-17 Decel Time 3
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-18 Accel Time 4
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-19 Decel Time 4
0.00~600.00 sec/0.00~6000.0 sec
10.00/
10.0
○
○
○
○
01-20 JOG Acceleration Time
0.00~600.00 sec/0.00~6000.0 sec
1.00/
1.0
○
○
○
○
01-21 JOG Deceleration Time 0.00~600.00 sec/0.00~6000.0 sec
1.00/
1.0
○
○
○
○
01-22 JOG Frequency
0.00~600.00Hz 6.00
○
○
○
○
○
01-23
1st/4th Accel/decel
Frequency
0.00~600.00Hz 0.00
○
○
○
○
01-24
S-curve for Acceleration
Departure Time 1
0.00~25.00 sec/0.00~250.0 sec
0.2/0.0
○
○
○
○
01-25
S-curve for Acceleration
Arrival Time 2
0.00~25.00 sec /0.00~250.0 sec
0.2/0.0
○
○
○
○
01-26
S-curve for Deceleration
Departure Time 1
0.00~25.00 sec /0.00~250.0 sec
0.2/0.0
○
○
○
○
01-27
S-curve for Deceleration
Arrival Time 2
0.00~25.00 sec /0.00~250.0 sec
0.2/0.0
○
○
○
○
01-28
Skip Frequency 1 (upper
limit)
0.00~600.00Hz 0.00
○
○
○
○
01-29
Skip Frequency 1 (lower
limit)
0.00~600.00Hz 0.00
○
○
○
○
01-30
Skip Frequency 2 (upper
limit)
0.00~600.00Hz 0.00
○
○
○
○
01-31
Skip Frequency 2 (lower
limit)
0.00~600.00Hz 0.00
○
○
○
○
01-32
Skip Frequency 3 (upper
limit)
0.00~600.00Hz 0.00
○
○
○
○
01-33
Skip Frequency 3 (lower
limit)
0.00~600.00Hz 0.00
○
○
○
○
01-34
Mode Selection when
Frequency < Fmin
0: Output Waiting
1: Zero-speed operation
2: Fmin (4th output frequency setting)
0
○
○
○
○
01-35
1st Output Frequency
0.00~600.00Hz 60.00/
○
○
○
○
○
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Содержание VFD-VE
Страница 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...