Chapter 4 Parameters
|
Revision Dec. 2008, 04VE, SW V2.05
4-129
Frequency
Time
Dwell at accel./decel.
07-16
Dwell
Frequency
at Accel.
07-15
Dwell Time
at Accel.
07-17
Dwell Time
at Decel.
07-18
Dwell
Frequency
at Decel.
07-19
Fan Control
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory Setting: 0
Settings
0
Fan always ON
1
1 minute after AC motor drive stops, fan will be OFF
2
AC motor drive runs and fan ON, AC motor drive stops and fan OFF
3
Fan ON to run when preliminary heat sink temperature (around
60
o
C
)
attained
4
Fan always OFF
This parameter is used for the fan control.
07-20
Torque Command
Unit: 0.1
Control
mode
TQCPG
Factory Setting: 0.0
Settings
-100.0 to 100.0%
(Pr. 07-22 setting=100%)
This parameter is torque command. When Pr.07-22 is 250% and Pr.07-20 is 100%, the actual
torque command = 250%X100% X motor rated torque.
The drive will record the setting before power off.
07-21
Torque Command Source
Control
mode
TQCPG
Factory Setting: 0
Settings
0
Digital
keypad
1
RS485 serial communication (RJ-11)
2
Analog
signal
(Pr.03-00)
When Pr.07-21 is set to 0, the torque command can be set in Pr.07-20.
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Содержание VFD-VE
Страница 1: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 2: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 3: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...
Страница 39: ...CALL NOW 800 985 6929 http www automatedpt com CALL NOW 800 985 6929 http www automatedpt com ...